To modify the alarm values automatically proceed as follows:
·
Select the required element from the configuration tree – a specific machine, for
example. The alarm values for this element and all sub-elements it contains are
modified.
·
Click on
Alarm thresholds
in the
System menu
.
Specify time range
You can use the
Time range
option to limit the measuring values used for
averaging. To do this, enter the start and end time. Alternatively, you can enter the
end time and specify the duration in whole days in the
No. of days
input field. In
the latter case the start time is automatically determined.
Configuration of automatic adjustment
Automatic adjustment of alarm values can be defined for each individual
characteristic value
(acceleration, demodulation, velocity and temperature) of
the element selected in the configuration tree.