background image

®

19 

Pool Equipment Tie In 

Once the plumbing is completed and ready to tie in 
to the solar array on the roof, the pluming is ready to 
be connected to the pool equipment.  

Note: It is critical to manually flush any debris 
out of the lines before connecting the solar array 
and the pool equipment.  

Follow these steps for flushing the lines: 
1.  Ensure all plumbing is connected except the cou-

plings to the solar array and the final lines at the 
pool equipment.  

2.  Manually plug the solar lines at the pool equip-

ment with a rag or loose pipe cap (or at the low 
point in the plumbing). 

3.  Using a garden hose, fill both supply and return 

lines with water at the high points in the system. 

4.  Allow the water to release from the lines and 

purge the debris from the plumbing system. 

5.  Repeat if necessary. 

Note: This procedure can also be performed by 
plumbing everything except the final connection 
to the collector banks and using the pool pump to 
circulate water to the roof.

 

Once lines are properly purged of any chips or other 
debris, both the solar array and the pool equipment 
can be connected. See 

Figure 2

 and 

Appendix E 

for a 

complete description of all necessary components at 
the pool equipment. 

Automating the solar pool heating system is not re-
quired, though is highly recommended by FAFCO

®

. Sys-

tems that are automated will be able to run when ambi-
ent conditions support pool heating. If the pool system 
is not automated, the solar system may be mistakenly 
left on when there is not adequate solar energy to heat 
the pool and could cause the pool to lose heat, thus 
countering the purpose of the solar heating system. In 
addition, a manual diverter valve can be left on and 
overheat the pool or cause a stagnation effect when the 
pump is turned off. 

Caution: Stagnated solar systems 

can trap water at scalding temperatures and result 
in severe burns if not treated properly.

 

Electrically operated solar controllers are available from 
a variety of manufacturers. When installing an automat-
ed system be sure to read and follow the directions for 
the controls equipment to ensure their proper operation.  
It is highly recommended that all solar systems be in-
stalled in conjunction with a pool automation system for 
optimum system performance. 

Thermal System Automation

 

Pool Plumbing

 

The solar thermal system is installed after the pump 
and filter but before additional pool equipment. (

Figure 

2

).  

 

Alternatively, if pool equipment is specifically la-

beled by manufacturer as to be installed before the solar 
equipment, then the it may be before the solar system. 
Such equipment may include intellichems, and Ultraviolet 
cleaning systems. 

The first component after the filter is a check valve. Al-
ways leave room for check valves to be cut out and re-
placed. The use of pool swing or spring check valves, 
such as the 7305 Jandy Pro Series, are recommended.  
Next, the diverter valve and PVC tees are installed. 
Install an isolation valve, such as a PVC ball valve or 
equivalent, on the piping going to the solar. Install a 
second isolation valve on the return line. If desired, a 
check valve can be used on the return line in place of the 
isolation valve. These components are always installed 
before any back up pool heaters or chlorinators. 

PHASE II 

 

System Installation Detail Cont’d

 

CAUTION: If the isolation valve on the return line 
were closed while the system was running, damage 
to the system would result from over-
pressurization.  

Always be sure to turn both valves when isolating the 
solar system from the main pool equipment. 
Manual solar drain valves are only recommended to 

be placed on plumbing lines which don’t drain when 

equipment is turned off. The primary purpose of man-
ual drain valves is to provide easy draining access for 
service and winterization.  

Drain valves should be installed in an accessible 
location at the lowest elevation possible and MUST 
adhere to the placement shown in Figures 2 and 
13.  

Flush out all pipes before they are connected to the 
thermal system as specified in 

Pool Equipment Tie In. 

Once plumbing is connected, ensure all lines exposed 
to the sun are properly protected from UV exposure. 
Most common practice is to thoroughly paint all 
plumbing.  

Note: If using 

Flexible PVC 

lines as a means of ab-

sorbing Thermal Movement, use multiple coats of 
paint or cover the segments with a UV burier such 
as a braded sheathing to keep the segment thor-
oughly protected from excessive UV exposure.

 

Summary of Contents for Sunsaver

Page 1: ... 1 Made in the U S A S o l a r P o o l H e a t i n g S y s t e m s FOR USE WITH SWIMMING POOLS TO HARNESS THE ENERGY OF THE SUN INSTALLATION MANUAL SUNSAVER ...

Page 2: ...rials Roof Penetrations Hybrid System Layouts PHASE II System Installation Detail Mounting Collectors Connect Supply Return Lines Obstacle Avoidance VRV End Caps Diverter Valve Pool Equipment Tie In Pool Plumbing Thermal System Automation PHASE III Commissioning Diverter Valve Pressure Leak Check Placement of Sensors System Automation Commissioning Documents Installation Manual Table of Contents 4...

Page 3: ...ces Various Plumbing Configurations and High Point Return Plumbing with Balancing Valves No High Point Return Plumbing Movement Bank and Plumbing Movement Appendix D Roof Mounting Details SunSaver Collectors on Composition Roofs SunSaver Collectors on Barrel Tile Roofs SunSaver Collectors on Flat Tile Roofs SunSaver Collectors Wood Rack Mounted SunSaver Collectors Metal Rack Mounted Appendix E Alt...

Page 4: ...O s goal has been to design test and produce the world s highest performing solar pool heating systems Installing a FAFCO solar pool heating system is straight forward and relatively simple This manual pro vides a step by step installation procedure for most applications For those situations not covered in this manual please contact your FAFCO representative Please read this manual completely befo...

Page 5: ...zing Drain at 45 F prior to Freezing Conditions Absorptivity 0 96 Emissivity 0 90 Thermal Specifications Thermal Energy Output 1800 Btu ft2 day System Operating Pressure 100 F At Bottom Header 30 psi System Intermittent Pressure 100 F At Bottom Header 40 psi Factory Test Pressure Burst Pressure Per Collector 50 psi 220 psi Recommended Flow Rate Per Collector 0 1 gal min ft2 Delta T at y intercept ...

Page 6: ... 06918 Black weather resistant polymer Mounts solar collector header and body straps to a roof or rack using a 1 4 lag bolt and cap 7 Cap 06919 Black weather resistant polymer Threads onto base to secure strap 8 21 2 Hose Clamp 02031 Stainless steel 21 2 hose clamp Secures Rubber Couplers to barbed fittings Tighten using flat head or 5 16 socket driver 9 Rubber Coupler 3 1 2 02033 31 2 long 23 8 i...

Page 7: ...ouplers 1 32 header strap 1 2 check valve 1 Owner s Manual 16 Add Bank Pack 154 Adds parts to terminate plumbing and mounting a bank One per added bank of collectors 1 vacuum relief valve 1 CPVC end cap 2 CPVC female adapters 7 tie down caps 7 tie down bases 6 clamps 1 3 1 2 coupler 2 5 couplers 1 32 header strap 17 Split Pack 155 Allows for space around an obstacle one per row space needed 18 Col...

Page 8: ...water remains on shut down 21 3 Way Diverter Valve Enables pool water to be directed to solar or directly to the pool return use in all solar equipped systems 22 Automated Solar Diverter Actuator Enables automatic movement of 3 way diverter valve use with pool automation and pool controllers 23 Pool Check Valve Prevents water from flowing in a reverse direction when unintended use after the pool f...

Page 9: ...ipment Aux Back Up Heater Not Shown Chlorinator Additional Pumps A Figure 3 Diverter Valve Schematic 1 2 3 5 6 7 9 8 11 12 13 15 14 4 16 17 10 Either Tee Upward or Opposing Corner Acceptable Manual Isolation Valve or Check Valve Permitted Optional Figure 2 Example SunSaver System The typical SunSaver solar pool system consists of a combination of FAFCO sourced parts and standard equipment The abov...

Page 10: ...ts The typical SunSaver solar pool system consists of a combination of FAFCO sourced parts and standard equipment The above figure and the component list below depicts common Array Layout Components and shows the proper placement of all components Legend for Figure 4 Array Layout Components SunSaver Collector 4ft wide SunSaver Collector 2ft wide not shown Vacuum Relief Valve End Cap Pipe Adapter B...

Page 11: ... installed under collectors It is typically acceptable to use Schedule 40 PVC for system plumbing In extreme conditions CPVC plumbing may be more applicable See Table 4 in Appendix C Flush out all pipes before connecting them to collectors in order to clear any chips which may have become trapped in the plumbing Systems with local lows in the plumbing should have a way of manually draining the lin...

Page 12: ...g added so that the bank can be plumbed around the obstacle Gaps can be filled by connecting PVC runs to Pipe Adapters and Couplers as depicted in Figure 10 Collector Layout Spacing Collectors and Penetrations Collectors will also grow or shrink along the length of the collector Be sure to mount collectors so that there is at least 2 of clearance from the bottom headers to any obstacles below the ...

Page 13: ...eturn line with a high point will enable a com parable backpressure on the return line of each bank and therefore match collector flow throughout the ar ray Unlike FAFCO CoolPV Systems SunSaver Systems do not utilize an individual high point return line When installing both SunSaver and CoolPV Systems plumbing must conform with the schematics in Figure 8 to ensure the system is properly balanced a...

Page 14: ...rection Two Plumbing Expansion Hoses are advised to accommodate this movement when the plumbing is strapped as shown Refer to Table 6 in Appendix C for recommended Plumbing Expansion Hose lengths In this case the movement in the bank corresponds to 1 2 which can also be transposed to an equivalent of 40ft PVC pipe Table 5 Additionally there is a 10ft line of PVC Adding the two provides 50ft of equ...

Page 15: ...nd pres sure specifications of white PVC by providing documen tation that it conforms to ASTM D1785 or an equivalent standard it should not be used for solar plumbing Due to the poor UV resistant properties of PVC it should be painted upon completion of the installation Plumbing Materials PHASE I Site Preparations Planning Cont d Hybrid System Layouts SunSaver collectors are compatible with most s...

Page 16: ...ding Note It is crucial that the collector couplers and hose clamps are installed properly If improperly positioned the hose clamps and couplers can move and the entire bank of collectors can expand severely under pressure causing the collector body to collide with roof mounted obstacles When installing mounting hardware it is best practice to use the premeasured method mentioned in Collector Layo...

Page 17: ...couplers to PVC Collectors PVC Pipe Pipe Adapter Hose Clamp Coupler Since the collectors are made of a polymer that sees large temperature swings there can be a lot of natural movement in an array as well as all plumbing If sim ple practices are not adhered to this natural move ment can cause damage to solar collectors plumbing and roof penetrations As seen in Phase I Plumbing Layout and Appendix ...

Page 18: ...ectors 2ft wide can be useful on roofs where there are multiple obsta cles to avoid and standard size collectors don t fit 3 Once all collectors have been positioned with clearance finish plumbing the collectors as de scribed in Phase I Mounting Collectors and Con nect Supply and Return Lines 4 After turning on the system ensure the banks have not moved too close to obstacles and address as needed...

Page 19: ... highly recommended that all solar systems be in stalled in conjunction with a pool automation system for optimum system performance Thermal System Automation Pool Plumbing The solar thermal system is installed after the pump and filter but before additional pool equipment Figure 2 Alternatively if pool equipment is specifically la beled by manufacturer as to be installed before the solar equipmen...

Page 20: ...the actuator repositions the valve when directed 2 Check that the set positions direct flow as ex pected Diverter Valve To ensure optimum performance it is highly recom mended to automate all solar thermal systems with an automation package of choice There are many auto mation packages which are available from pool suppli ers such as Pentair Jandy and Hayward It is recom mended by FAFCO to source ...

Page 21: ...rtup for SunSaver solar collectors is essen tially the opposite order of winterizing but also includes checking for leaks and any damage which could have occurred during the winter season Typically a system should be recommissioned for sum mer use whenever ambient temperatures and sunshine is able to produce reasonable heat to exchange with the pool The startup season will vary by location but is ...

Page 22: ...tion Valves Winter OFF Summer ON 7 2 Automation Winter OFF Summer ON 3 Drain Valves Winter Open Summer Closed 1 Figure 13 Solar System Maintenance Figure 13 depicts the components to decommission remove or reinstall during sys tem Winterization Summerization or when performing other routine maintenance ...

Page 23: ... If the collector is still under manufacturer s warranty contact FAFCO to determine replacement eligibility IMPORTANT Attempts to repair SunSaver collec tors by any other means will void FAFCO s Manu facturer s Warranty All repairs are only to be per formed by a FAFCO Authorized installing compa ny Do not attempt to apply screws epoxy or any other types of sealant Collector Repairs NOTE All collec...

Page 24: ...entered between collectors when system is running at operating temperatures The SunSaver system must be capable of draining if not manual drain valves should be installed or a winterization service must be in place All plumbing in the system must hold under pressure without leaking All plumbing in the system utilizes a standard method to allow for thermal movement If used all Flexible PVC lines ar...

Page 25: ...s layout for this system has been attached _____________________________________ Authorized SunSaver Installer Date ___ ___ _____ Pressure Difference ______________________________psi Roof Orientation Circle all that apply for installations across multiple roof pitches N NE E SE S SW W NW A copy of the Dealer s layout for this system has been sketched Home Owner ___________________________________...

Page 26: ...rtical Head Loss ft Head Loss in other Pool Equipment ft Total Head Loss ft Total Head Loss psi Box A Box B Box C Box D Box E Box F Box G Box H Box I Box J Box K Box L Box M Box N Box O Box P Box Q Box R Box U Box S Box T Box V Box W Box X A E B F C G D H I J K L Box P result M N Box Q 5 1 ft ea panel Table A2 from box S T O Pump to top header height R U V W X 0 43 total pipe length used Box Y Los...

Page 27: ...ound to 40 0 028 8 1 Vertical Head Loss ft 24 Head Loss in other Pool Equipment ft 32 14 psi Total Head Loss ft 85 FT Total Head Loss psi 36 PSI Box A Box B Box C Box D Box E Box F Box G Box H Box I Box J Box K Box L Box M Box N Box O Box P Box Q Box R Box U Box S Box T Box V Box W Box X A E B F C G D H I J K L Box P result M N Box Q 5 1 ft ea panel Table A2 from box S T O Pump to top header heigh...

Page 28: ... 28 Example Manufacturer s Pump Curves APPENDIX B Pump Sizing 40 GPM 85FT 40 GPM 85 FT Recommended Pump Speed Curve Recommended Setting ...

Page 29: ...allation Use this table in cases where less than 2 nominal may be needed For example if there is an obstacle on the right of the second collector to the right of the fixed collector 2 collector gaps there should be 1 2 clearance from the obstacle Maximum pressures that CPVC and PVC piping can withstand at higher temperatures Table 4 CPVC vs PVC Temperature F 80 90 100 110 120 130 140 150 160 170 1...

Page 30: ...ine Multi Bank SunSaver Pool Systems utilize a common high point return line enabling each bank to have proportional feed and return line backpressures which limits the water to favor the path of least resistance Notice I is an example of a stacked Reverse Return and II is stacked Same End Return I STACKED REVERSE RETURN II STACKED SAME END RETURN SPLIT FEED REVERSE RETURN ...

Page 31: ... have proportional feed which limits the water to favor the path of least resistance Notice A is an example of a Reverse Return Multi Bank system where the balancing valves are needed and B is a Single Bank Reverse Return which doesn t need balancing valves Similarly C is an example of a Same End Return Multi Bank system where the balancing valves are needed and D is a Single Bank Same End Return ...

Page 32: ...such as an offset should be used so that the line can move as needed Refer to Table 5 for Regular PVC Joint Offset lengths and offset type for a length of pipe Regular PVC Pipe 2X Straight Line Plumbing Fixed Support Guide Supports Fixed Support 4ft Length of Pipe To accommodate for long plumbing runs refer to the table or incorporate an industry standard plumbing offset If space doesn t permit it...

Page 33: ...7 6 0 7 1 8 1 9 2 10 3 11 3 12 4 13 4 Expansion Dimensions Chart for PVC Line Offsets with 3 5 Couplers in Line T 80 F Most Installations Most Installations with Bank Movement Uncommon Installations Length of Pipe ft 10 20 30 40 50 60 70 80 90 100 Thermal Expansion in 0 6 0 8 1 2 1 5 1 8 2 1 2 4 2 7 3 0 3 3 Leg L 4 in 8 7 9 2 9 8 10 4 10 9 11 4 12 0 12 5 13 0 13 5 Leg L 2 in 17 4 18 4 19 7 20 7 21...

Page 34: ...ing movement needed See Table 6 in Appendix C for details It is recommended for the Fix Mounted Collector to be at a the centermost point in a bank as seen in image C of Figure 22 when possible DIAGRAM LEGEND Guide Support Fixed Support Plumbing Expansion Joint Fixed Points 4ft Fix Mounted Collector Bank Moves up to 5X 1 4 2 5 Collector 0 Collector 1 Collector 2 Collector 3 Collector 4 Collector 5...

Page 35: ... recom mended to put a burier between the lower headers and the roof for extra roof protection of the roof when the collectors move with temperature fluctuations Note All mounting hardware must be installed with care Seal all roof penetrations according to an industry standard method NOTE If local codes allow the bolt to be secured only into the sheathing be sure not to overtighten bolts Figure 23...

Page 36: ...e must be used to support the collector from excessive sagging Note All mounting hardware must be installed on a runner and the runner must be mounted into the roof with the same number of penetrations Seal all roof penetrations according to an industry stand ard method Standing Seam Metal Roofs not depicted Mounting substrate and runners fall under the same parameters as in Tile Roof Mounting Roo...

Page 37: ...bstrate is required to support and protect the collec tors from abrasion but may be substituted by a roof rack with support from runners not exceeding 16 separation If the rack has spacing greater than 16 a substrate must be used to support the collector from excessive sagging Figure 25A Tile Stand Off Method Figure 25B Tile Clip Method ...

Page 38: ...if the rack has runners at a minimum spacing of 16 If the rack has spacing greater than 16 a substrate must be used to support the collector from excessive sagging Panels are to be installed no more than 20 vertical feet below pool sur face to the bottom header due to static head pressure at stagnation tem peratures Figure 26 Wood Ground Rack Mounting ...

Page 39: ... if the rack has runners at a minimum spacing of 16 If the rack has spacing greater than 16 a substrate must be used to support the collector from excessive sagging Panels are to be installed no more than 20 vertical feet below pool surface to the bottom header due to static head pressure at stagnation temperatures Figure 27 Metal Ground Rack Mounting ...

Page 40: ...quires Manual Draining To Pool To Solar From Pool To To Solar From Pool To Pool To Solar From Pool To Solar From Pool To Pool SOLAR OFF SOLAR ON SOLAR OFF SOLAR ON Figure 28 DiverterValve on Supply Isolation on Return Aux Heater optional Pool Chlorinator optional Filter Pump Check Valve Diverter Valve Isolation Valves Solar Drain Valves optional Automation Equipment recommended To Solar From Solar...

Page 41: ...m Pool To Pool SOLAR OFF SOLAR ON SOLAR OFF SOLAR ON The below figures depict alternate types and locations of the diverter valve and check isolation valve Non draining configurations should be manually drained for winter self draining systems do not require draining for winterization Aux Heater optional Pool Chlorinator optional Filter Pump Check Valve Diverter Valve Isolation Valves Solar Drain ...

Page 42: ...epict alternate types and locations of the diverter valve and check isolation valve Non draining configurations should be manually drained for winter self draining systems do not require draining for winterization Aux Heater optional Pool Chlorinator optional Filter Pump Check Valve Diverter Valve Isolation Valves Solar Drain Valves optional Automation Equipment recommended To Solar From Solar Inl...

Page 43: ...1 DiverterValve on Return CheckValve on Return The below figures depict alternate types and locations of the diverter valve and check isolation valve Non draining configurations should be manually drained for winter self draining systems do not require draining for winterization Check Valve Isolation Valve Aux Heater optional Pool Chlorinator optional Filter Pump Check Valve Diverter Valve Isolati...

Reviews: