5. PROGRAMMING
To program operation of the automated system, you have to access the “PROGRAM-
MING” mode.
Programming is split into two parts: BASIC and ADVANCED.
5.1. BASIC PROGRAMMING
To access BASIC PROGRAMMING, press key
F
:
•
if you press it (and hold it down), the display shows the name of the
fi
rst function.
•
if you release the key, the display shows the value of the function that can be
modi
fi
ed with keys
+
and
-
.
•
if you press
F
again (and hold it down), the display shows the name of the next
function, etc.
•
when you reach the last function, press
F
to exit the program, and the display
resumes showing the gate status.
The following table shows the sequence of functions accessible in BASIC PRO-
GRAMMING:
BASIC PROGRAMMING F
Display
Function
Default
LO
FUNCTION LOGICS (see tab. 3/a - h):
A
=Automatic
AP
=“Stepped” automatic
S
= “Safety” Automatic
E
= Semi-automatic
EP
= “Stepped” Semi-automatic
C
= Dead-man
b
= “B” Semi-automatic
bC
= Mixed Log. (
b
opening /
C
closing)
EP
PA
PAUSE TIME:
This has effect only if the automatic logic was selected. Adju-
stable from
0
to
59
sec. in one-second steps.
Subsequently, display changes to minutes and tens of secon-
ds (separated by a point) and time is adjusted in 10-second
steps, up to the maximum value of
4.1
minutes.
E.g. if the display shows
2.5
, pause time is 2 min. and 50 sec.
2.0
F0
FORCE:
Adjusts Motor thrust.
01
= minimum force
50
= maximum force
20
d1
OPENING DIRECTION:
Indicates the gate opening movement and makes it possible
not to change the motor and limit-switch connections on the
terminal board.
-3
= Right-hand opening movement
3-
= Left-hand opening movement
-3
St
GATE STATUS:
Exit from programming and return to gate status viewing.
00
= Closed
01
= Now opening
02
= Stopped
03
= Open
04
= Pause
05
= “FAIL SAFE” tripped (chpt. 5.2)
06
= Now closing
07
= Now reversing
08
= Photocells tripped
5.2. ADVANCED PROGRAMMING
To access ADVANCED PROGRAMMING, press key
F
and, as you hold it down,
press key
+
:
•
if you release key
+
, the display indicates the name of the
fi
rst function.
•
if you release key F too, the display shows the value of the function that can be
modi
fi
ed with keys
+
and
-
.
•
if you press key
F
(and hold it down), the display shows the name of the next fun-
ction, and if you release it, the value that can be modi
fi
ed with keys
+
and
-
is shown.
•
when you reach the last function, press
F
to exit the program, and the display
resumes showing the gate status.
The following table shows the sequence of functions accessible in ADVANCED
PROGRAMMING:
ADVANCED PROGRAMMING F + +
Display
Function
Default
b0
MAXIMUM TORQUE AT INITIAL THRUST:
The motor operate at maximum torque (ignoring the torque set-
ting) at start of movement. Useful for heavy leaves.
Y
= Active
no
= Disabled
Y
Sr
SLOW MOVEMENT EVERY TIME POWER IS TURNED ON /
RESTORED
:
Y
= Enabled
no
= Not enabled
no
br
FINAL BRAKING:
When the gate engages the opening or closing limit-switch, a
braking stroke can be selected to ensure the leaf is stopped
immediately. If decelerations are selected, braking starts when
they
fi
nish.
At
00
value, braking is disabled.
Time can be adjusted from
01
to
20
sec. in 0.1-second steps.
E.g. if the display indicates
10
, braking time is 1 second.
00
= Braking disabled
from
01
to
20
= Timed braking
05
FS
FAIL SAFE TEST ON FSW CL AND FSW OP INPUTS
If this function is activated, it enables a function test of the pho-
tocells before any gate movement. If the test fails (photocells
not serviceable signalled by value
05
on the display), the gate
does not start moving.
Y
= Active
no
= Disabled
no
SA
FAILSAFE TEST ON EDGE INPUT
This function allows the failsafe test to be enabled at the EDGE
input.
Y
= Active
no
= Disabled
no
PF
PRE-FLASHING (5 s):
Activates the
fl
ashing lamp for 5 seconds before start of mo-
vement.
no
= Disabled
oP
= Only before opening
CL
= Only before closing
OC
= Before every movement
no
SP
INDICATOR-LIGHT:
If
00
is selected, the output functions as a standard indicator-
light (lighted at opening and pause,
fl
ashing at closing, and off
when gate closed).
Courtesy light:
Different
fi
gures correspond to timed activation
of the output, which can be used (by a relay) to power a courtesy
lamp. Time can be adjusted from
0
to
59
sec. in 1-second steps,
and from
1.0
to
4.1
min. in 10-second steps.
Electric lock command and ‘traf
fi
c lights’ functions:
If you press key
-
from the
00
setting, the command for the
E1
closing electric lock is activated;
If you press
-
again, the command for the
E2
closing and opening
electric lock is set;
if you press the
-
key again, you can set the ‘traf
fi
c lights’ fun-
ctions
E3
and
E4
.
00
= Standard indicator-light
from
01
to
4.1
= Timed output.
E1
= electric lock command before opening movement
E2
= electric lock command before opening and closing mo-
vements
E3
= ‘traf
fi
c lights’ function: the output is active in “open” and
“open on pause” status and is disabled 3 seconds before the
closing manoeuvre starts.
There is 3 seconds of pre-
fl
ashing before the closing
manoeuvre.
E4
= ‘traf
fi
c lights’ function: the output is active only in “closed”
status.
Do not exceed the output’s maximum load (24Vdc-3W).
If necessary, use a relay and a power supply source
outside the equipment.
00