FAAC GENIUS Sprint 382 Manual Download Page 8

SPRINT  382  -  SPRINT  383 

00058I0112        -  Rev.6

Tr

ansla

tion of the original instruc

tions

ENGLISH

5. PROGRAMMING

To program operation of the automated system, you have to access the “PROGRAM-
MING” mode. 
Programming is split into two parts: BASIC and ADVANCED.

5.1. BASIC PROGRAMMING

To access BASIC PROGRAMMING, press key 

F

:

• 

if you press it (and hold it down), the display shows the name of the 

fi

 rst function.

• 

if you release the key, the display shows the value of the function that can be 
modi

fi

 ed with keys 

+

 and 

-

.

• 

if you press 

F

 again (and hold it down), the display shows the name of the next 

function, etc.

• 

when you reach the last function, press 

F

 to exit the program, and the display 

resumes showing the gate status.

The following table shows the sequence of functions accessible in BASIC PRO-
GRAMMING:

BASIC PROGRAMMING  F

Display

Function

Default

LO

FUNCTION LOGICS (see tab. 3/a - h):

A

 =Automatic

AP

 =“Stepped” automatic 

S

 = “Safety” Automatic

E

 = Semi-automatic

EP

 = “Stepped” Semi-automatic

C

 = Dead-man

b

 = “B” Semi-automatic

bC

 = Mixed Log. (

b

 opening / 

C

 closing)

EP

PA

PAUSE TIME:

This has effect only if the automatic logic was selected. Adju-
stable from 

0

 to 

59

 sec. in one-second steps.

Subsequently, display changes to minutes and tens of secon-
ds (separated by a point) and time is adjusted in 10-second 
steps, up to the maximum value of 

4.1

 minutes.

E.g. if the display shows 

2.5

, pause time is 2 min. and 50 sec.

2.0

F0

FORCE:

Adjusts Motor thrust.

01

 = minimum force

50

 = maximum force

20

d1

OPENING DIRECTION:

Indicates the gate opening movement and makes it possible 
not to change the motor and limit-switch connections on the 
terminal board.

-3

 = Right-hand opening movement 

3-

 = Left-hand opening movement

-3

St

GATE STATUS:

Exit from programming and return to gate status viewing.

00

 = Closed

01

 = Now opening

02

 = Stopped

03

 = Open

04

 = Pause

05

 = “FAIL SAFE” tripped (chpt. 5.2)

06

 = Now closing

07

 = Now reversing

08

 = Photocells tripped

5.2. ADVANCED PROGRAMMING

To access ADVANCED PROGRAMMING, press key 

F

 and, as you hold it down, 

press key 

+

:

• 

if you release key 

+

, the display indicates the name of the 

fi

 rst function.

• 

if you release key F too, the display shows the value of the function that can be 
modi

fi

 ed with keys 

+

 and 

-

.

• 

if you press key 

F

 (and hold it down), the display shows the name of the next fun-

ction, and if you release it, the value that can be modi

fi

 ed with keys 

+

 and 

-

 is shown.

• 

when you reach the last function, press 

F

 to exit the program, and the display 

resumes showing the gate status.

The following table shows the sequence of functions accessible in ADVANCED 
PROGRAMMING:

ADVANCED PROGRAMMING  F  +  +

Display

Function

Default

b0

MAXIMUM TORQUE AT INITIAL THRUST:

The motor operate at maximum torque (ignoring the torque set-
ting) at start of movement. Useful for heavy leaves.

Y

 = Active

no

 = Disabled

Y

Sr

SLOW MOVEMENT EVERY TIME POWER IS TURNED ON / 
RESTORED

:

 

Y

 = Enabled

 

no

 = Not enabled

no

br

FINAL BRAKING:

When the gate engages the opening or closing limit-switch, a 
braking stroke can be selected to ensure the leaf is stopped 
immediately. If decelerations are selected, braking starts when 
they 

fi

 nish.

At 

00

 value, braking is disabled. 

Time can be adjusted from 

01

 to 

20

 sec. in 0.1-second steps.

E.g. if the display indicates 

10

, braking time is 1 second.

00

 = Braking disabled

from 

01

 to 

20

 = Timed braking

05

FS

FAIL SAFE TEST ON FSW CL AND FSW OP INPUTS

If this function is activated, it enables a function test of the pho-
tocells before any gate movement. If the test fails (photocells 
not serviceable signalled by value 

05

 on the display), the gate 

does not start moving.

Y

 = Active 

no

 = Disabled

no

SA

FAILSAFE TEST ON EDGE INPUT

This function allows the failsafe test to be enabled at the EDGE 
input.

Y

 = Active 

no

 = Disabled

no

PF

PRE-FLASHING (5 s):

Activates the 

fl

 ashing lamp for 5 seconds before start of mo-

vement.

no

 = Disabled

oP

 = Only before opening 

CL

 = Only before closing

OC

 = Before every movement 

no

SP

INDICATOR-LIGHT:

If 

00

 is selected, the output functions as a standard indicator-

light (lighted at opening and pause, 

fl

 ashing at closing, and off 

when gate closed).

Courtesy light:

 Different 

fi

 gures correspond to timed activation 

of the output, which can be used (by a relay) to power a courtesy 
lamp. Time can be adjusted from 

0

 to 

59

 sec. in 1-second steps, 

and from 

1.0

 to 

4.1

 min. in 10-second steps.

Electric lock command and ‘traf

fi

 c lights’ functions:

If you press key 

-

 from the 

00

 setting, the command for the 

E1 

closing electric lock is activated;

If you press 

-

 again, the command for the 

E2 

closing and opening 

electric lock is set;

if you press the 

key again, you can set the ‘traf

fi

 c lights’ fun-

ctions 

E3

 and 

E4

.

00

 = Standard indicator-light

from 

01

 to 

4.1

 = Timed output.

E1

 = electric lock command before opening movement

E2

 = electric lock command before opening and closing mo-

vements

E3

 = ‘traf

fi

 c lights’ function: the output is active in “open” and 

“open on pause” status and is disabled 3 seconds before the 
closing manoeuvre starts.

There is 3 seconds of pre-

fl

 ashing before the closing 

manoeuvre.

E4

 = ‘traf

fi

 c lights’ function: the output is active only in “closed” 

status.

 Do not exceed the output’s maximum load (24Vdc-3W). 

If necessary, use a relay and a power supply source 
outside the equipment.

00

Summary of Contents for GENIUS Sprint 382

Page 1: ...print 382 Sprint 383 Translation of the original instructions Traductiondelanoticeoriginale bersetzung der Original Anleitung Traducci ndelmanualoriginal Vertalingvandeoorspronkelijkegebruiksaanwijzin...

Page 2: ...crushing safety device consisting of a torque control Nevertheless its tripping threshold must be checked as specified in the Standards indicated at point 10 16 The safety devices EN 12978 standard pr...

Page 3: ...INPUTS CHECK page 7 7 AUTOMATED SYSTEM TEST page 7 EU DECLARATION OF CONFORMITY The Manufacturer Company name FAAC S p A Soc Unipersonale Address Via Calari 10 40069 Zola Predosa BOLOGNA ITALY hereby...

Page 4: ...rd inputs Open P artial opening Safety devices at opng Safety devices at clsng Stop Edge Power supply Earth On connector inputs Opening and closing limit switches Encoder Terminal board outputs Flashi...

Page 5: ...against the risk of impact Opening closing safety devices they operate during the gate opening and closing movements and therefore they are suitable for protecting the opening and closing areas again...

Page 6: ...PEN A Total Opening command terminal 1 any pulse generator push button detector etc which by closing a contact commands total opening and or closing of the gate leaf To install several total opening p...

Page 7: ...essories terminals 7 and 8 24 Vdc Positive for power supply to accessories terminals 9 and 10 Accessories max load is 500 mA To calculate absorption values refer to the instructions for individual acc...

Page 8: ...e sequence of functions accessible in ADVANCED PROGRAMMING ADVANCED PROGRAMMING F Display Function Default b0 MAXIMUM TORQUE AT INITIAL THRUST The motor operate at maximum torque ignoring the torque s...

Page 9: ...ng to the performed deceleration spaces 2 0 ADVANCED PROGRAMMING F Display Function Default AS ASSISTANCE REQUEST combined with next function If activated at the end of countdown settable with the nex...

Page 10: ...No effect OPEN disabled No effect No effect OPEN disabled OPEN on PAUSE Stops operation Stops operation No effect Reloads pause time OPEN disabled No effect OPEN disabled ON CLOSING Re opens the leaf...

Page 11: ...o effect OPEN disabled No effect No effect OPEN disabled OPEN Re closes the leaf immediately Stops operation No effect No effect OPEN disabled ON CLOSING Stops operation No effect saves OPEN see parag...

Page 12: ...effect OPEN A B disabled Tab 3 h LOGIC BC OPENING PULSES CLOSING COMMANDS ALWAYS PRESSED PULSES GATE STATUS OPEN A opening OPEN B closing STOP OPENING SAFETY DEVICES CLOSING SAFETY DEVICES OP CLOS SA...

Page 13: ...746 E R 41 732099 Rev D...

Page 14: ......

Page 15: ...icherheitsvorrichtungen Norm EN 12978 erm glichen den Schutz eventueller Ge fahrenbereiche vor mechanischen Bewegungsrisiken wie zum Beispiel Quetschungen Mitschleifen oder Schnittverletzungen 17 F r...

Page 16: ...Sede legale FAAC S p A Soc Unipersonale Via Calari 10 40069 Zola Predosa BOLOGNA ITALY Tel 39 051 61724 Fax 39 051 09 57 820 www geniusg com SPRINT 382 SPRINT 383 12 00058I0112 Rev 6...

Reviews: