ADVANCED PROGRAMMING 

Display

 

Function

dF01

Po

POSITION OF DOOR:

Shows the position of the door during motorised movement from

 

00

 

to

 

59

.

For an explanation of parameter

 

PO

 

refer to chapter

 

7.5

.

00

P1

UPPER LIMIT OF ZONE A:

Defines the upper limit of zone 

A

, in which to subsequently adjust the force, speed and sensitivity functions of 

the encoder 

F1

S

1

E1

(input value

 

P1

 

as explained in chapter 

7.5

).

 

20

P2

UPPER LIMIT OF ZONE B:

Defines the upper limit of zone

 

B

,

 in which to subsequently adjust the force, speed and sensitivity functions of 

the encoder

 

F2

S2

E2

(input value

 

P2

 

as explained in chapter 

7.5

).

 

32

oF

OPENING FORCE:

Adjusts force during opening from

 

01

 

to

 

50

.

25

F2

CLOSING FORCE IN ZONE B:

Adjusts force during closing from

 

01

 

to

 

50

.

30

F1

CLOSING FORCE IN ZONE A:

Adjusts force during closing from

 

01

 

to

 

50

.

20

S2

CLOSING SPEED IN ZONE B:

Adjusts  closing speed in zone B from

 

01

 

to

 

10

(

10

 

= max. speed,

 

01

 

= min. speed).

05

S1

CLOSING SPEED IN ZONE A:

Adjusts closing speed in zone A from 

01

 to 

10

(

10

 = max. speed, 

01

 = min. speed).

03

E2

ENCODER SENSITIVITY IN ZONE B:

Adjusts anti-crushing sensitivity in zone B from 

01

 to 

50

(

50

 = min. sensitivity, 

01

 = max. sensitivity).

04

E1

ENCODER SENSITIVITY IN ZONE A:

Adjusts anti-crushing sensitivity in zone A from 

01

 to 

50

(

50

 = min. sensitivity, 

01

 = max. sensitivity).

03

LP

COURTESY LIGHT:

To set lighted time of the courtesy light.
Can be adjusted from

 

0

 to 

59

 sec in one-second steps.

Afterwards, the viewing changes in minutes and tenths of a second (separated by a dot) and time is adjusted 

in 10 second steps, up to the maximum value of 

4.1

 minutes.

E.g. if the display shows 

2.5

, the pause time will be 2 min and 50 sec.

30

Tab. 3

Summary of Contents for E550

Page 1: ...E550...

Page 2: ...ety of people it is important that you read all the following instructions Incorrect installation or incorrect use of the product could cause serious harm to people Carefully read the instructions bef...

Page 3: ...r Coupling to 5 pin Minidec board Decoder Receiver RP RP2 Terminal board inputs removable Open Encoder Opening safety devices Closing safety devices Opening limit switch Closing limit switch Flashing...

Page 4: ...creasing the system s safety level If the Failsafe control isdisabled theterminalisanegativeforsupplytoaccessories 5 FCA Opening Limit switches contact N C The opening limit switch consists of a micro...

Page 5: ...facing the board Insert and remove the board ONLY after cutting power A two digit display is installed on the board During normal operation it indicates the status of the inputs We show below the exa...

Page 6: ...puts status The following table Tab 2 indicates the sequence of functions accessible in BASIC PROGRAMMING Tab 2 7 3 ROTATION DIRECTION CHECK Procedure for checking exact connection of motor phases 1 P...

Page 7: ...etely 11 Wait for the motor to stop 12 Take a note of the value indicated on the display as the value of parameter P2 for subsequent input e g P2 32 13 Input values P1 and P2 which you had annotated i...

Page 8: ...closing from 01 to 50 30 F1 CLOSING FORCE IN ZONE A Adjusts force during closing from 01 to 50 20 S2 CLOSING SPEED IN ZONE B Adjusts closing speed in zone B from 01 to 10 10 max speed 01 min speed 05...

Page 9: ...8 AUTOMATED SYSTEM TEST When you have finished programming check if the system is operating correctly Check if force is adequately adjusted and if the safety devices operate correctly Also run the imp...

Page 10: ...h pre flashing selected movement begins after the set pre flashing time When the Encoder is tripped this causes stop at opening and reverse at closing Tab 4 c Tab 4 d LOGIC A PULSES STATUS OF THE AUTO...

Page 11: ......

Page 12: ...com au INDIA FAAC INDIA PVT LTD Noida Delhi India tel 91 120 3934100 4199 www faacindia com SWITZERLAND FAAC AG Altdorf Switzerland tel 41 41 8713440 www faac ch CHINA FAAC SHANGHAI Shanghai China te...

Reviews: