5.3 CONNECTIONS
F
Carry out the connections with the power supply
disconnected.
CONTROL DEVICES
i
Multiple NO contacts on same input must be con-
nected in parallel.
Multiple NC contacts on same input must be con-
nected in series.
Below is a brief explanation of the inputs. The effect
a command has may vary according to the operating
logic and programming functions.
■
Connecting the devices to terminal board J3:
LOCK
MAIN
LAMP
M1
M2
IN1 IN2 IN3 IN4 IN5
F
+
/R1
-
/R2
M
M
230V~
60W max
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22
27 28 29
23
24
25
26
RADIO
RP/DEC
2EASY
CONNECTIVITY
CR2032
USB-A
EDGE1
OUT1
CO
M
OP
CL
PE
N
L
CO
M
O
P-
A
+24V
+24V
-
-
-
-
OP
-B
ST
OP
FSW CL
FSW OP
OP
CL
OUT2
LOCK1 LOCK2
EDGE2
FCC2
FCA2
FCC1
FCA1
230V~
C
C
J3
9 OP-A
(IN1)
(TOTAL motion command)
NO contact, connect a push-button or another type
of pulse generator which, by closing a contact, com-
mands the total opening (OPEN) of the gate.
10 OP-B
(IN2)
(Motion command determined by the set operating
logic)
NO contact, connect a push-button or another type
of pulse generator which, by closing a contact, causes
the gate to close (CLOSE in logics
c
,
b
,
bC
) or PARTIAL
open (in all other logics):
The partial opening is:
• 50% of the complete opening in systems with only
one motor
• complete only for the leaf actuated by motor 1 in
two motor systems
11 STOP
(IN3)
(Stop command)
NC contact, connect a push-button or another type of
pulse generator which, by opening a contact, causes
the automation to stop.
i
If the input is not used, bridge it with the
common contacts (-).
12 FSW CL
(IN4)
(Photocells active during closing)
NC contact, connect a photocell or another device
that, by opening the contact during closing, reverses
the gate.
It can be configured to reverse immediately or when
the photocell is released by setting programming
function
Ph
.
i
If the input is not used, bridge it with the
common contacts (-).
13 FSW OP
(IN5)
(Photocell active in opening)
NC contact, connect a photocell or another device
that, by opening the contact during opening, reverses
the gate.
i
If the input is not used, bridge it with the
common contacts (-).
14…16
-
Common contacts / Accessories power supply negative
■
Connecting the devices to terminal board J11:
LOCK
MAIN
LAMP
M1
M2
IN1 IN2 IN3 IN4 IN5
F
+
/R1
-
/R2
M
M
230V~
60W max
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22
27 28 29
23
24
25
26
RADIO
RP/DEC
2EASY
CONNECTIVITY
CR2032
USB-A
EDGE1
OUT1
CO
M
OP
CL
PE
N
L
CO
M
O
P-
A
+24V
+24V
-
-
-
-
OP
-B
ST
OP
FSW CL
FSW OP
OP
CL
OUT2
LOCK1 LOCK2
EDGE2
FCC2
FCA2
FCC1
FCA1
230V~
C
C
J11
27 EDGE1
(Safety in opening devices active)
Connect a sensitive edge that, when activated during
opening, causes the gate to reverse.
This input can be configured by setting programming
function
So
to connect:
• sensitive edges with NC contact -default-
• resistive sensitive edges 8.2 kΩ
i
If the input is not used, bridge it with the
common contacts (-).
28
-
Common contacts / Accessories power supply negative