Advanced function
DEFAULT:
0 1 2 3 4 5 6 7
Ad
ADMAP FUNCTION
Enables/disables operation in accordance with French
standard NFP 25/362.
Y
enabled,
no
disabled
no
EC
ANTI-CRUSHING SENSITIVITY
This function defines the speed with which
the anti-crushing system triggers after an obstacle has been detected.
01
minimum
10
maximum
(* = not modifiable)
01
*
06 06 05 06 05 05 06
US
ULTRA-SENSITIVE OBSTACLE DETECTION
This function allows a rigid impact
to be recognised immediately.
Y
enabled,
no
disabled
no no no no Y Y Y no
r8
SEARCH FOR STOP
NOT displayed if
FC
or
FA
=
01
. This function
specifies the angular space in which to search for the opening/closing stop. In
this space, the automation is stopped by a mechanical stop/obstacle and not
by the anti-crushing system.
0.3
…
9.9
° Adjustment step: 0.1 ° Displayed in degrees and tenths of
a degree (separated by a point) up to 9.9°, then it is in degrees.
10
…
20
° Adjustment step: 1 °
10 10 10 4.0 10 4.0 4.0 1
SF
SOFT TOUCH
NOT displayed if
En
=
Y
. This function causes the leaf to
reverse slightly after the mechanical stop has been detected.
Y
enabled,
no
disabled
no
o1
OUT1
Function of output OUT1.
The letters
tr
indicate TIMER programming (from Simply Connect, not
modifiable from the board).
00
00
disabled
01
FAIL-SAFE
02
LED
03
COURTESY LIGHT (timed)
04
ACTIVE ERROR
05
automation OPEN or PAUSED
06
automation CLOSED
07
automation MOVING
08
automation IN EMERGENCY
09
automation OPENING
10
automation CLOSING
11
electric lock function (timed)
12
SAFETY DEVICE ACTIVE
13
TRAFFIC LIGHT function (active during
OPENING and with automation OPEN)
14
timed output that can be activated
from the 2
nd
radio channel OMNIDEC
15
output (step-by-step function) that
can be activated from the 2
nd
radio channel
OMNIDEC
16
active during the movement of motor
1
17
active during the movement of motor
2
18
anti-intrusion alarm
19
battery operation
t1
TIMING OUT1
Displayed if
o1
=
03
,
11
,
14
. Sets the duration of
output OUT1, if a timed function is programmed.
1
…
59
min
Adjustment step:
1 min (if
o1
=
03
or
14
), 1 s (if
o1
=
11
)
02
o2
OUT2
Function of output OUT2 (with the same options as
o1
).
The letters
tr
indicate TIMER programming (from Simply Connect, not
modifiable from the board).
02
t2
TIMING OUT2
Displayed if
o2
=
03
,
11
,
14
. Sets the duration of
output OUT2, if a timed function is programmed.
1
…
59
min
Adjustment step: 1 min if
o2
=
03
or
14
, 1 s if
o2
=
11
01