B614
42
732998 - Rev.A_DRAFT
Tr
ansla
tion of the original instruc
tions
ENGLISH
8.3
SET-UP
The set-up procedure enables the limit switch posi-
tions to be memorised.
The system needs to be set-up:
-
When the automation system is first started
-
When the board has been replaced
-
Each time the display shows
50
flashing and the
automation system does not work
-
Following any variation in the position of the limit
switch.
How to perform the set-up:
!
During the SET-UP, the safety devices are ignored, keep
away and stop anyone from approaching the automation
system until the end of the procedure
The SET-UP MUST be performed:
- with the mains power switched on
- with the automation system functioning automatically
- with the STOP/EMER inputs not active
1. Select parameter
tL
in Basic Programming, the
display shows
--.
:
2. Keep the buttons pressed
+
and
-
around 3
seconds. When
S1
appears flashing, release the
buttons. The beam begins to close and stops
when it reaches the stop.
3.
S2
flashes on the display. The beam remains in
the closure position for a couple of seconds.
4.
S3
flashes on the display. The beam begins to
open and stops when it reaches the stop.
5. The procedure has come to an end and the display
shows the status of the open automation system
(
01
).