15. INTERCOM
■
DESCRIPTION
The A951 is capable of communicating with other
A951 units via an Intercom network connection. This
enables the following functions to be used (KP EVO
menu 2.6.1):
-
INTERMODE: a master door from which to set the
operating mode for all the other doors that are
connected to the network.
-
INTERLOCK: two single doors, where the opening
of one is subject to the closing of the other and
vice versa.
-
2 LEAVES: access consisting of a double leaf.
-
2 INTERLOCK: two interlocked accesses,
each consisting of a double leaf.
!
Every network connected A951 should be pro-
grammed for the same Intercom mode.
In order to build the communication network, an
optional accessory Communication board must be
installed on each A951
■
CONNECTION
The units in the network are connected via 3 cascade
connected-wires between the J2 connectors of the
Communication boards (
53
).
!
The sequence in which the units are wired is unim-
portant, but it is essential that a CASCADE connection
is used.
The 2 DIP switches on the Communication board must
be set as follows:
-
On the first and last units of the cascade connec-
tion: both ON.
-
On intermediate units (if any): both OFF.
■
ADDRESSING
A unique ID (KP EVO menu 2.6.2) must be assigned to
each A951 in the network as indicated below.
!
Do not assign the same ID to more than one unit in
the network.
■
REGISTRATION
After having wired up and assigned an address to each
unit (menu 2.6.3 of the KP EVO), registration must only
be carried out on the A951 that has been assigned ID1.