background image

24

ENGLISH

the operator on the lintel (fig. 7).

2)

Insert the roller (3) inside the sliding guide (4) (fig. 7).

3)

Pull arm (1) inwards manually as shown in fig. 7(b) and
secure the sliding guide (4) by means of two M6 screws on
the closed door as shown in Table D.

4)

Check manually that the door is free to open and close
fully and comes to rest against the mechanical end stops.
If the door does not close correctly, adjust the return spring
as described in section 10.

4. START-UP

1)

Make the electrical connections to the 960 MP electronic
control unit as described in section 6.
To gain access to the control unit, pass the cables through
the special conduit (fig. 1 - ref. 1) as shown in fig. 8.

2)

Fit the two end covers and connect up the function switch.
The end cover with the switch may be fitted on the right or
the left. For cable routing refer to fig. 8.

3)

Turn the operating function switch (fig. 1 - ref. 12) to
position I (

AUTOMATIC 

logic).

4)

Check that the programming unit microswitches (fig. 10)
are all in the 

OFF 

position.

Important

: When mounting the “pulling articulated” or “sliding”

arms or for opening angles greater than 90

°

, turn 

microswitch

no. 2 to ON 

before connecting power to the system.

5)

Close the door.

6)

Power up the operator. Powering is signalled by an acoustic
signal from a buzzer.

7)

Check that the 5V LED on the programming unit (fig. 9)
lights up.

8)

At the end of the initialisation procedure, check the status
of the signalling LEDs on the programming unit as shown in
Table 5.

Table 5: Operation of status LEDs

LED

ON

OFF

5 V

logic powered

logic not powered

OK

command active

command inactive

YES

safety devices active

safety devices inactive

N.B.:

 The status of the LEDs with the door closed at rest is shown

in bold type.

4.1. INITIALISATION PROCEDURE

As soon as the system is powered up, it runs an initialisation
procedure which includes setting the following parameters:
- measuring the mass of the door;
- determining the end stop positions;
- determining the point at which the STOP safety device

intervenes (see  section 6).

The door opens at low speed, then closes half way before
switching back to opening.
Subsequent closure is performed by the return spring.
The initialisation procedure is indicated by an intermittent
acoustic signal (frequency 1 sec) emitted by a buzzer on the
programming unit (table 6).
The process may be inhibited due to:
- function switch in the 0 (MANUAL) position;
- incorrect connection of the accessories (electric lock,

control/safety devices);

- incorrect positioning of the programming unit microswitches.

N.B.:

 To repeat the initialisation procedure hold down the RESET

button (fig. 11 - ref. 4) for more than 4 seconds.

5. 961 B-E PROGRAMMING UNIT

5.1 LAYOUT AND DESCRIPTION

5.2. SETTING THE ADJUSTING TRIMMERS

The programming unit features trimmers (fig. 9 - ref. 3) which
regulate the following parameters:

Trimmer Vo

 to set the opening speed.

Setting 30 

÷

 100% of the initialisation value.

Standard setting 50%.

Trimmer Vc 

to set the closing speed.

Setting 30 

÷

 100% of the initialisation value.

Standard setting 50%.

N.B.: 

The speed initialisation values depend on the dimensions

and the mass of the door.

Trimmer To

 to set the pause time (AUTOMATIC logic).

Setting from 1 to 30 seconds.
Standard setting 3 seconds.

Trimmer Fm

 to set the pulling force of the operator.

Setting 60 

÷

 100% of maximum value.

Standard setting 100%.
Turn the trimmers clockwise to increase the values of the
settings.
Turn the trimmers anticlockwise to reduce the values of the
settings.

with 960 MP electronic control unit

f

Encoder

g

Connector (2 pole) for connection

with 960 MP electronic control unit

a

Signalling LEDs (see Table 5)

b

Signalling buzzer (see section 5.4.)

c

Adjusting trimmer

d

Programming microswitches

e

Connector (16 pole) for connection

1 2 3 4 5 6

S1

S2

S3

S4

S5

S6

Fm

To

Vc

Vo

SI

OK

5V

4

3

2

1

7

6

5

Fig. 9

Summary of Contents for 961 B-E

Page 1: ...ubsequent amendments 91 368 EEC 93 44 EEC and 93 68 EEC complieswiththeessentialsafetyrequirementsinthefollowingEECDirectives 73 23 EEC and subsequent amendment 93 68 EEC 89 336 EEC and subsequent ame...

Page 2: ...with an opening distance of the contacts of 3 mm or more Alternatively use a 6A thermomagnetic breaker with multi pole switching 12 Ensure that there is a differential switch up line of the electrica...

Page 3: ...automatic unit for swing doors is a one piece unit consisting of an electromechanical device that allows door opening to be controlled by means of a driving arm The door is re closed by a spring syst...

Page 4: ...the operator transmission shaft by means of the extension and the screw 4 provided fig 5 The arm must be mounted perpendicular to the closed door N B If a greater distance between the operator and the...

Page 5: ...nitialisation procedure which includes setting the following parameters measuring the mass of the door determining the end stop positions determining the point at which the STOP safety device interven...

Page 6: ...buzzer which emits sequences of acoustic signals corresponding to different statuses of the system The statuses that have occurred and their identification sequence can be seen in Table 6 Table 6 Aco...

Page 7: ...contacts 11 12 13 14 15 16 EMERGENCY CLOSURE OPENING STOP SAFETY CLOSURE SAFETY 24 Vdc 0 Vdc 0 Vdc INTERNAL COMMAND 0 Vdc 8 9 10 EXTERNAL COMMAND 0 1 2 230 V 6 10 50 60 Hz 1 2 3 white brown green 0 V...

Page 8: ...then re closes after the pause time POSITION 0 MANUAL NIGHT The position 0 can be used to select two different operating functions according to the programming carried out on the 961 B E programming u...

Page 9: ...mme and monitor the operation of the system If the CODIS is used permanently it is necessary to activate function 7 at Level III programming functions see paragraph 8 3 For the electrical connection o...

Page 10: ...L III PROGRAMMING FUNCTIONS The CODIS has a programming level where certain functions can be selected These functions are required for several special applications Note a voltage drop or a RESET comma...

Page 11: ...n N O contact terminals 18 19 960MP Door open closed indication N C contact the open and closed positions of the door are indicated by the opening of a N C contact terminals 18 19 960MP function 12 Al...

Page 12: ...the inner door LED 6 lights up select the SLAVE option on the CODIS unit of the outer door LED 6 goes out Function 16 select the desired option on both the CODIS programming units IMPORTANT the interl...

Page 13: ...th the door closed draw a vertical line on the spring as shown in figure 30 Open the door and check the state of the line figure 30 shows two possible configurations In case B fig 30 lubricate the spr...

Page 14: ...mains open o LED 4 AUTOMATIC The door opens when internal or external commands are active and re closes after the pause time o LED 3 AUTOMATIC SPARE o LED 2 ONE WAY Entry or exit inhibited only one di...

Reviews: