29

ENGLISH

ENGLISH

3

Electric lock - N.C. contact (max. capacity 0.5 A/24 V) (fig.14).

The output is suitable for commanding a magnetic closure
system. If no power is supplied, the electric lock is not active.
In the NIGHT function the electric lock is powered and hence
active. In the event of an opening command (internal
command or EMERGENCY OPENING), the power supply to
the electric lock is temporarily cut off to allow the door to be
opened.

4

Door status CLOSED - N.O. contact (max. capacity 0.5 A/24 V).

When the door CLOSED position is reached, the contact
closes.

5

Door status - Common

6

Door status OPEN - N.O. contact (max. capacity 0.5 A/24 V).

When the door OPEN position is reached, the contact closet.

J

6 terminal board

 Relay outputs and special functions (figs.

17, 18, 19)

Description of the terminal board

20

Changeover relay - Common

21

Changeover relay - N.O. Contact

This output is activated (N.C.) by the Card Reader input for
2 sec.
Attention: this output is not suitable for controlling electric
locks.

22

Changeover relay - N.C. Contact

This output is activated (N.O.) by the Card Reader input for
2 sec.
Attention: this output is not suitable for controlling electric
locks.

23

Alarm Output - Common

24

Alarm Output - N.O. Contact

This output is activated (N.C.) if an alarm is present. At the
same time LED2 on the 950 I/O board lights up to indicate the
alarm condition.

25

+24Vdc

+24Vdc accessories power supply

26

GND

Accessories power supply Negative and contacts Common

27

“Interlock”output

This terminal is used to enable communication between two
950BM automated systems programmed in “Interlock”
configuration, see par. 11.1.

28

“2 Leaves” output

This terminal is used to enable communication between two
950BM automated systems programmed in “2 Leaves”
configuration, see par. 11.2.

8. FUNCTION SELECTOR SWITCH

The 950 BM operator has a 3-position function selector switch (0-1-2) mounted on one side of the cover (fig. 4 - ref. 2). The selector
switch position is fixed: however, depending on the type of installation (on doorpost or on lintel), the connection cable to the 950I/
O unit must be positioned as shown in figs. 4a/b. The selector switch can be easily inspected by opening the protection door (fig.
4 - ref.1).
The selectable operating functions are shown in fig. 20.

1

0

2

POSITION "1": OPEN

When this function is selected, the door opens and remains open.

POSITION "0": AUTOMATIC

If this function is selected, when an internal/external command is given, the door opens and then
re-closes after the pause time.

POSITION "2": MANUAL/NIGHT

The position “2” can be used to select two different operating functions according to the
programming carried out on the 950 MPS programming unit (see paragraph 5.4.3). The two
functions are:

MANUAL:

 The door can be opened manually.

NIGHT:

 The external command is inactive. The door can be opened solely by activating the Key

command (fig. 11) .

7. INSTALLING THE CASING

The closure casing is designed so that the styling does not
change although the operator can be mounted either on
the door or on the lintel. Plug in the function selector switch
(fig.4-ref.2) connection cable to the 950 I/O electronic unit,
using the quick-fit connector. According to type of installation
and to ensure the cable is correctly laid, refer to figures 4a
and 4b. Slide the closing plug (fig.4-ref 4) inside the top slot
of the casing.  Make sure that the screws (fig.4-ref3) are not
fully tightened on the fixing brackets of the casing.  Position
the black plastic doors (fig. 4-ref1) on the seats at the sides
of the closure casing.  Fit the cover as shownin fig. 4. Tighten
the screws (fig.4-ref 3) to secure the cover in its position and
close the doors (fig.4 ref.1). Snap-fit the closing plug on the
bottom slot of the cover (fig.4-ref 5).

J7 Connector

  Quick-fit connector for connecting RP plug-

in Receivers or Minidec/Decoder decoding cards (fig.
10).

J9 TERMINAL BOARD 

NOT-AUS stop terminal board (fig. 10)

Description of the terminal board

N.C. contact for emergency stop. If there is no connection
between the two terminals, the automated system is locked
and cannot perform any electrical movement.

J10 Connector

  Quick-fit connector for 40Vdc power supply

to 950 MPS board (fig.10)

J11 Connector

  Quick-fit connector for door status signals

to 950 MPS (fig.10)

Fig. 20

Summary of Contents for 950 BM

Page 1: ...950BM 950BM para la naturaleza 100 papel reciclado ist umweltfreundlich 100 Altpapier pour la nature papier recycl 100 for nature recycled paper 100 carta riciclata 100 per la natura...

Page 2: ...Fig 2a Fig 2b Fig 3 1 1 2 2 3 3 1 2 4 5 Fig 4 Fig 4b Fig 4a 6...

Page 3: ...Fig 5 Fig 6...

Page 4: ...onter plus de 2 rallonges Cota con eje est ndar Si fuera necesario aumentar la distancia entre el actuador y el brazo utilizar las prolongaci nes modulares opcionales Cada prolungaci n aumenta la altu...

Page 5: ...pas monter plus de 2 rallonges Cota con eje est ndar Si fuera necesario aumentar la distancia entre el actuador y el brazo utilizar las prolongaci nes modulares opcionales Cada prolungaci n aumenta la...

Page 6: ...pas monter plus de 2 rallonges Cota con eje est ndar Si fuera necesario aumentar la distancia entre el actuador y el brazo utilizar las prolongaci nes modulares opcionales Cada prolungaci n aumenta l...

Page 7: ...pas monter plus de 2 rallonges Cota con eje est ndar Si fuera necesario aumentar la distancia entre el actuador y el brazo utilizar las prolongaci nes modulares opcionales Cada prolungaci n aumenta l...

Page 8: ...under the provisions of Directive 98 37 EC conforms to the essential safety requirements of the following EEC directives 73 23 EEC and subsequent amendment 93 68 EEC 89 336 EEC and subsequent amendme...

Page 9: ...ol Board 950 MPS Power supply 230 Vac 6 10 50 60 Hz Accessories power supply 24 Vdc 500mA max Electric lock power supply N O N C 24 Vdc 500mA max Standard operating functions selector switch Open Auto...

Page 10: ...lesarenotinacentral position see Mounting tables The holes are offset in order to ensurethattheoperatorismountedwiththecorrectdirectionof rotation of the mechanism The mounting tables are the followin...

Page 11: ...in Table 7 N B The default status of the LEDs with the door closed at rest is shown in bold type Table 7 Operation of the status signalling LEDs for 950 I O board LED ON OFF LD1 Accessories power pre...

Page 12: ...ostrongwind accordingtoitsstructureanddimensions as this could activate the system s spontaneous opening or motionreversing 5 4 5 MICROSWITCHES Nos 5 6 8 9 INACTIVE 5 4 6 MICROSWITCH No 7 STOP SAFETY...

Page 13: ...llel 12 Emergency Command N C Contact Any pulse generator normally a pushbutton which by openingacontact commandsanemergencyclosureofthe system Alternatively this input can be used to command emergenc...

Page 14: ...J5 TERMINAL BOARD Connection to relay Outputs figs 13 14 15 Description of the terminal board 1 Electric lock Common 2 Electric lock N O Contact max capacity 0 5 A 24 V fig 13 Ifnopowerissuppliedtheel...

Page 15: ...able to the 950I O unit must be positioned as shown in figs 4a b The selector switch can be easily inspected by opening the protection door fig 4 ref 1 The selectable operating functions are shown in...

Page 16: ...loading rotate the arm in closing direction until the next fixing position of the stop point screw fig 21 ref 5 is in line with the inspection slot and fix the screw again 5 Reinstall the arm correctl...

Page 17: ...ntroller to the 950 I O control board by a 2x0 5mm max 50m cable Fig 24 If the two LOCK terminals are connected to each other as shown in Fig 24 all keys on the programmer are disabled 10 3 DIAGNOSTIC...

Page 18: ...ctivated The internal and external radars are disabled The Key command causes opening and closing after the night pause time elapses standard 7 sec Adjusting range of night pause time from 0 to 30 sec...

Page 19: ...eys or to select sub menu or parameter and confirm with the OK key An asterisk on the display indicates the currently active setting To exit programming select the exit function at each level Otherwis...

Page 20: ...ENGLISH Diagram 3 Setup Diagram 4 Lock SETUP 80 7 SEC 2 SEC CLOSING STANDARD NO STANDARD OBSTACLE DETECTION NIGHT PAUSE TIME PARTIAL OPENING PAUSE TIME EXIT LOCK OFF ON ALWAYS ONE WAY NIGHT NIGHT KIT...

Page 21: ...950 v DIAGNOSTICS NR CYCLE XXXX ALARM N alarm description PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 KEEP SETTINGS OFF ON 8 8 EXIT ADVANCED MENU OPERATION PARAMETERS CLOSING SPEED OPENIN...

Page 22: ...Out Setup PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 PASSWORD 0000 IN OUT SETUP EMERG OPEN CLOSE OUT OP CL NO OUT ALARM NO NC USCITA NC NO NC ADVANCED MENU OPERATION PARAMETERS VARIOUS EXIT CHANGE PASS...

Page 23: ...00 IN OUT SETUP STAND SETUP STANDARD NO STANDARD INTERLOCK MASTER SLAVE NO MEMORY WITH MEMORY EXIT NEW PASSWORD 0000 NEW PASSWORD 0000 NEW PASSWORD 0000 NEW PASSWORD 0000 MASTER SLAVE ON OFF ON OFF 2...

Page 24: ...E BAND 4 FUN 0 00 00 TIME BAND 3 FUN 0 00 00 TIME BAND 1 FUN 0 00 00 TIME BAND 2 FUN 0 00 00 TIME BAND 5 FUN 0 00 00 TIME BAND 4 FUN 0 00 00 TIME BAND 3 FUN 0 00 00 TIME BAND 1 FUN 0 00 00 TIME BAND 2...

Page 25: ...rocedure and if the cause of signalled malfunction was removed it restores normal operation 5 ADVANCED MENU PASSWORD To access the advanced menu insert the 4 digit password default 0000 1 OPERATION PA...

Page 26: ...can create up to 5 different time bands for each day of the week by setting the band starting time and assign an operational function to each time band When the KP Controller s internal clock reaches...

Page 27: ...or to close totally in order to activate the sensor of the second door 6 Door B opens Fig 28 Door A Door B 7 The person exits 8 Door B closes after the night pause time elapses The operation is identi...

Page 28: ...s is immediately reversed The partial opening function enables control of total opening of the master only The operating functions must be set on the master automated system only or on the KP Controll...

Page 29: ...sshouldbefollowed to prevent problems from arising accidentally Do not stand or allow children or adults to stand within range of the door especially during operation and do not leave objects near it...