Closing the contact between terminals 3-4 activates the electric
lock(s) present.
With the FAACTOTUM it is possible to program this contact to
close as follows:

- only when the gate starts to open
- only when the gate starts to close
- when the gate starts to open and when it starts to close.

Module MEL 2

The module MEL-2 (Fig. 18) is able
to control 2 inputs for
independent electric locks. Two
free contacts are available
between terminals 3 (COM), 5
(N.O.) and 6 (N.O.).
Following the connection
diagram shown in Fig. 19, a
maximum of two 12 Vdc electric
locks with 12 ohm internal
resistance can be installed.
It is possible to install different
types of electric locks or a number
of electric locks in parallel using
external power sources following
the connection diagram shown
in Fig. 20.
In this case do not exceed the
maximum allowed capacity of
the contacts (2 A max.).

Single-leaf automation

In single-leaf automation the 

closure

 electric lock (Fig. 19) or

electric locks (Fig. 20) must be connected to terminal 6, while
the 

opening

 electric lock (Fig. 19) or electric locks (Fig. 20) must

be connected to terminal 5.

Double-leaf automation

In double-leaf automation the electric lock (Fig. 19) or electric
locks (Fig. 20) of leaf 1 (connected to motor M1) must be
connected to terminal 6, while the electric lock (Fig. 19) or
electric locks (Fig. 20) of leaf 2 (connected to motor M2) must
be connected to terminal 5.
Closing the contacts between terminals 3-5 and 3-6 activates
the electric lock(s) connected to them.
By using the FAACTOTUM these contacts can be programmed
to close as follows:
- only when the gate starts to open
- only when the gate starts to close
- when the gate starts to open and when it starts to close.

Fig. 18

Fig. 19

1 :

negative

2 :

positive

3 :

free common contact

5 :

free contact (N.O.)

6 :

free contact (N.O.)

 

1

 

2

 

3

 -

+

 5

 6

+

+

-

-

EL 2

EL 1

EL 1 - EL 2 :
12Vdc 12ohm electric locks

MEL-2

 

1

 

2

 

3

 -

+

 5

 6

EL 1

EL 2

EL 3

EL 4

V 1

V 2

N.B.: 

the maximum

capacity of the
contacts is 2A.

V1 - V2 :
External power
supplies

EL1-EL2-EL3-EL4 :
Electric locks

Fig. 20

MEL-2

Fig. 17

External power
supply

N.B.

 the maximum capacity

of the free contact is 5A.

 

1

 

2

 

3

 

4

 -

+

EL 2

EL 1

EL1 - EL2 :
Electric locks

MEL-1

MEI module

The MEI module (Fig. 21) is an
electronic input expansion card.
It must be inserted in the 460P
card connector J1. It must not be
installed on top of any electric
lock management modules
already present in the connector
J1.
On the MEI module there are 6
additional inputs with respect to
the standard 5 of the 460P
electronic card described above.

Fig. 21

Summary of Contents for 460-P

Page 1: ...reundlich 100 Altpapier pour la nature papier recycl 100 for nature recycled paper 100 per la natura carta riciclata 100 para la naturaleza 100 papel reciclado C ERME T A Z I E N D A C E R TIF I C A T...

Page 2: ...control unit model 460P complies with the essential safety requirements of the following directives 73 23 EEC and subsequent amendment 93 68 EEC 89 336 EEC and subsequent amendment 92 31 EEC and 93 6...

Page 3: ...s turn off the system s main switch 12 An omnipower switch shall be provided for the installation with an opening distance of the contacts of 3 mm or more Alternatively usea6Athermomagneticbreakerwith...

Page 4: ...supply 24 Vdc Max accessories load 0 5 A Warning light power supply 24 Vdc Max warning light load 3 W Temperature range 20 C 55 C Fuses Motors power supply Accessories power supply Logic power supply...

Page 5: ...ing 4 IN4 FSW CL Closing safety device contact N C During closure activation of the safety devices causes the gate leaves to reverse their direction of movement They are not activated during opening I...

Page 6: ...N4 IN5 FSW CL FSW OP One pair of opening photocells connected TX RX 7 6 10 11 Fig 7 J2 IN4 IN5 FSW CL FSW OP One pair of closure photocells connected TX RX 7 6 10 11 Fig 6 J2 IN4 IN5 FSW CL FSW OP One...

Page 7: ...ing light 24 Vdc 3 W max must be inserted between this terminal and the positive of the accessories power supply terminal 10 or 11 Do not exceed the stated power Table 5 Warning light standard operati...

Page 8: ...card 460P connector J1 or into the connector on the component side of another module The connector on the component side can be used to fit another module or the FAACTOTUM connection cable into the mo...

Page 9: ...he electric lock Fig 19 or electric locks Fig 20 of leaf 1 connected to motor M1 must be connected to terminal 6 while the electric lock Fig 19 or electric locks Fig 20 of leaf 2 connected to motor M2...

Page 10: ...alled on the leaf connected to the motor M1 LEAF 1 Limit switch used FCA1 N C Input for Leaf 1 opening limit switch contact The limit switch is a device with an N C contact which slows down the leaf c...

Page 11: ...signed default terminal on the 460P card e g the STOP function cannot be assigned to terminal IN5 on the 460P card 7 Each terminal with the exception of IN1 and IN2 can be deactivated by selecting the...

Page 12: ...effect OPEN CLOSE inhibited FSW OP no effect OPEN inhibited stops opening and when disengaged closes no effect opening inhibited no effect no effect opening inhibited FSW CL no effect no effect freeze...

Page 13: ...re safety device and one as an opening safety device 7 J2 IN4 IN5 FSW CL FSW OP 6 10 11 Fig 27 9 J2 IN4 IN5 FSW CL FSW OP Connection of a pair of closure photocells TX RX 7 6 10 11 Fig 28 9 J2 IN4 IN5...

Page 14: ...FE OP AND SAFE CL INPUTS using 460P standard configuration and MEI module FAILSAFE disabled No safety device connected A pair of opening closing photocells connected SAFE OP CL A closing pneumatic saf...

Page 15: ...OP 6 CLOSE 7 SAFE CL 8 SAFE OP 9 EMERG 10 11 Deceleration timed with limit switch with Gatecoder Opening inversion stroke Closure inversion stroke Opening over pushing stroke Closure over pushing stro...

Page 16: ...se a poner al d a la presente publicaci n todas las modificaciones que considere oportunas para el perfeccionamiento t cnico o para cualquier otro tipo de exigencia de car cter constructivo o comercia...

Reviews: