Connector J1
Optional modules (MEI - MEL1 - MEL2) and/or the FAACTOTUM
connection cable must be inserted in connector J1 (Fig. 14).
The connector can be fitted one way only so that the module
terminal block is oriented in the same direction as the 460P card
terminal block. Disconnect power from the card before inserting
or removing the modules.
3. INSTALLATION
Install the electronic control unit in enclosures with adequate
housing protection (min. IP55).
The cable holes and tube grips used for wiring must not reduce
the housing protection of the enclosure.
The 460P is provided with standard preset programming (the
characteristics are given in Table 2). For details of operation,
refer to Table 9.
Ü
The inputs CLOSE, SAFE-OP, SAFE-CL and EMERG are
available only by installing the input expansion module MEI
on the card (it is not necessary to program with the
FAACTOTUM).
3.1 CHECKING DIRECTION OF ROTATION
1)
Turn off power supply to 460P card.
2)
Move the gate or barrier manually to its halfway open
position.
3)
Lock the operators again.
4)
Turn the power supply back on.
5)
Send an opening pulse and check that this opens the leaf
or the barrier.
If the first opening pulse closes one or both leaves, invert the
electric motor phases (brown and black cables) on the card
terminal block for each leaf that closes.
Fig. 14
Fig. 15
4. OPTIONAL MODULES
The optional modules are additional electronic cards installed
on the 460P.
Each module has two connectors: one on the soldered side, the
other on the component side.
The connector on the soldered side allows the module to be
inserted into card 460P connector J1 or into the connector on
the component side of another module.
The connector on the component side can be used to fit
another module or the FAACTOTUM connection cable into the
module.
The currently available modules are:
MEL-1
: single electric lock management module.
MEL-2
: double electric lock management module.
MEI
: input expansion module.
The electric lock management modules must not both be
installed on the same 460P card.
One input expansion module (MEI) and one electric lock
management module (MEL-1 or MEL-2) can be installed, bearing
the following in mind:
The MEI module must be fitted into the 460P card connector J1
and the electric lock management module must be fitted on
top of the MEI module.
The connecting cable to the FAACTOTUM must be inserted into
the 460P card connector J1 if it is free (i.e. when no other
optional module is installed) or into the free connector of the
last installed module.
Module MEL-1
The module MEL-1 (Fig. 15) is able
to control either just one electric
lock or a number of electric locks
activated simultaneously (using
an external power supply). A free
contact is available between
terminals 3 (COM) and 4 (N.O.).
In the connection diagram shown
in Fig. 16, just one 12 Vdc electric
lock with 12 ohm internal
resistance must be installed.
A different type of electric lock or
a number of electric locks in
parallel can be installed using an
adequate external power supply
as shown in the diagram in Fig. 17.
In this case do not exceed the
maximum permitted contact
capacity (5A max.).
Ü
The MEL-1 module can be installed on the 460P card
without it being necessary to perform any programming
when using a closure electric lock.
1
2
3
4
-
+
+
-
EL
Fig. 16
1 :
negative
2 :
positive
3 :
free common contact
4 :
N.O. free contact
EL : 12Vdc 12 ohm electric lock
MEL-1