Pag e 20
M a y, 20 06
4 1 5 L LS Ope ra tor And
4 5 5 D C ontrol Pa ne l I nsta ll a ti on Ma nua l
However, if enabled, you cannot
adjust
this
opening delay of the operator connected to
Motor 2.
The closing leaf-delay time is adjustable from 0 to
4 minutes.
N
OTE
:
If the opening/closing time is set at
less than the leaf delay time, the delayed leaf
closes at the end of the closing time.
P
ROGRAMMING
To program the automated system, the
“Programming Mode” must be accessed.
Programming is split into two parts: BASIC and
ADVANCED.
R
ESTORE
THE
D
EFAULT
S
ETTINGS
To restore the default settings of the programming
press the three program buttons (+, —, F )
simultaneously and keep them pressed for five (5)
seconds.
B
ASIC
P
ROGRAMMING
To access BASIC PROGRAMMING, press the
“F”
key.
•
If you press it (and hold it down), the display
shows the name of the first function.
•
If you release the key, the display shows the
value of the function that can be modified with
keys
+
and
—
.
•
If you press and hold down the
“F”
key again
(and hold it down), the display shows the
name of the next function, etc.
•
When you reach the last function, press
“F”
to
exit the program, and the display resumes
showing the status of the inputs.
The table on the right shows the sequence of
functions accessible in BASIC PROGRAMMING.
BASIC PROGRAMMING
Display Function
Default
O
PERATING
L
OGICS
A = Automatic (Timer to Close)
E = Semi Automatic
S = Security
EP = (Semi-Automatic) Step by Step
AP = Stepped Automatic
B = Manned, Pulsed
C = Manned, constant
P
AUSE
T
IME
This is the time between open and
closing and is adjustable from 0 to
4 min. This is only true in “A”
Mode. (see pause time description)
F
ORCE
/T
ORQUE
M
OTOR
1
This adjusts the force / torque that
motor 1 is applying to the gate
leaf. Setting is 0 to 50.
*
F
ORCE
/T
ORQUE
M
OTOR
2
This adjusts the force / torque that
motor 2 is applying to the gate
leaf. Setting is 0 to 50.
*
C
LOSING
L
EAF
D
ELAY
Delays the closing of operator
wired into motor one outputs. Ad-
justable from 0 to 4 minutes
(Same as pause time)
M
OTOR
R
UN
T
IME
This enables where you choose
from “simple” learning or
“complete” learning of the motor
run time. See page 10 & 11 for
complete details.
Simple Learning
~ 1 s.
Complete Learning
> 3 s.
E
XIT
P
ROGRAMMING
Exit from programming and return
to display of inputs status.
+
F
+
*
With Hydraulic operators the Force/Torque must be set to
the maximum setting of 50.
PROGRAM BUTTONS
+ -
F
LEFT MIDDLE RIGHT
T
HE
45
5 D
C
ONT
R
OL
P
ANE
L
I
N
STALLA
T
ION
I
NSTR
UCTI
ONS