Step
Action
2
Mount the safety wire in the chimney (1). Use the
supplied screw and rawl-plug in brick chimney and the
self-cutting screw in steel chimney. Then mount the wire
through the hole in the base plate and into the wire lock.
Tighten the safety wire slightly and tighten the wire lock
(2), so that the chimney fan is secured when opened for
service and cleaning purposes.
The isolation switch should be fitted onto the side of the
chimney (3), so it is easily accessible when servicing the
fan. The armoured cable should be connected into the
underside of the isolator and up into the switch via the
coupling.
3
Before starting up, make sure that:
- the nuts in the location brackets are tightened (4)
- the chimney fan is closed and the screw
tightened (5)
- the safety wire is clamped to the chimney (6)
- the safety wire and the wire lock are tightened (7)
- the grommet on the armoured cable is fastened (8)
- the end-user is aware of the fact that the chimney fan
must always be operating when the fireplace/boiler is
in use