Powerware
®
Plus 12 Operator's Manual (164200090 Rev E)
i
This manual contains important instructions for your Powerware
®
Plus 12
Uninterruptible Power Supply (UPS) that should be followed during installation and
maintenance of the UPS, battery, and I/O cabinets.
To avoid equipment damage or personnel injury, use extreme care when handling the
cabinets. Cabinet weights range from 180 lb (82 kg) to 300 lb (136 kg). Before
transporting, test lift and balance the cabinets. Minimum tilt from vertical must be
maintained at all times. The pallet supports the cabinets only if the forks are completely
beneath the unit.
Since the UPS may contain batteries, the hazard of electric shock is present even when
the power processor is off. To avoid any release of sulfuric acid vapors, maintain
batteries below the maximum recommended temperature. Refer battery servicing to
qualified service personnel only.
In the event of a fire involving the UPS and its batteries, use only carbon dioxide fire
extinguishers or those approved for use in electrical fire fighting.
Because lethal voltages exist within the UPS during operation, extreme caution is
necessary when performing maintenance. Be sure to observe all warnings and
cautions in this manual. Make sure that qualified service personnel perform the
procedures when noted in the instructions. Failure to comply may result in serious
injury or death. When the UPS is in Maintenance Bypass mode, UPS components are
deĆenergized with the exception of EMI capacitors, output terminals, bypass
contactors, bypass control board, breakers, and battery cabinet. To achieve complete
isolation, remove all input and battery power. Some cabinet components are not
connected to chassis ground. A lethal shock hazard exists when any contact between
floating circuits and the chassis occurs.
The Powerware Plus 12 UPS contains high DC and AC voltages. If you turn off the input
power and disconnect the batteries, the high voltage at the filter capacitors and power
circuits is discharged to under 30 Vdc within five minutes. In the event of a power
failure, you should make the assumption that high voltage still exists after shutdown.
Use voltmeters to check AC and DC voltage before making contact.
If you plan to use test equipment while the UPS has power, you must isolate both the
test personnel and test equipment from direct contact with earth ground and the UPS
chassis frame using rubber mats.
Safety Considerations
The UPS contains LETHAL VOLTAGES. All repairs should be performed
by trained service personnel. There are no userĆserviceable parts inside the UPS.
The UPS contains its own energy source (battery). The output
receptacles may be live even when the UPS is not connected to an AC supply.
There is high voltage present at terminals 9 and 10 (terminals for remote battery
connection) when a battery cabinet is connected to the UPS.
Summary of Contents for powerware plus
Page 1: ... OPERATOR S MANUAL ...
Page 12: ...Powerware Plus 12 Operation ...
Page 35: ... Powerware Plus 12 Operator s Manual 164200090 Rev E 35 ...
Page 52: ...Description Outline Drawing PWP 18 Drawing No 110719045 Revision A Sheet 1 of 1 ...
Page 53: ...Description Oneline and Installation PWP 18 Drawing No 110719046 Revision A1 Sheet 1 of 2 ...
Page 54: ...Description Oneline and Installation PWP 18 Drawing No 110719046 Revision A1 Sheet 2 of 2 ...
Page 57: ...Description Three Phase PDM Installation PWP 18 Drawing No 110719090 Revision A1 Sheet 1 of 1 ...
Page 58: ...Description PWP18 Schematic Drawing No 110712322 Revision A Sheet 1 of 1 ...
Page 59: ...Description I O Outline and Installation PWP18 Drawing No 110719176 Revision B Sheet 1 of 1 ...
Page 60: ...Description I O Cabinet Oneline PWP 18 Drawing No 110719175 Revision C1 Sheet 1 of 5 ...
Page 61: ...Description I O Cabinet Oneline PWP 18 Drawing No 110719175 Revision C1 Sheet 2 of 5 ...
Page 62: ...Description I O Cabinet Oneline PWP 18 Drawing No 110719175 Revision C1 Sheet 3 of 5 ...
Page 63: ...Description I O Cabinet Oneline PWP 18 Drawing No 110719175 Revision C1 Sheet 4 of 5 ...
Page 64: ...Description I O Cabinet Oneline PWP 18 Drawing No 110719175 Revision C1 Sheet 5 of 5 ...