3 UPS Operations
Powerware
®
Plus 12 Operator's Manual (164200090 Rev E)
17
To switch to Bypass (with Bypass Configuration switch enabled), hold the UPS Off
button for three seconds. The Normal indicator goes off and the Bypass indicator
illuminates.
If the alarm sounds when the UPS Off button is pressed, then Bypass is
not available. If the UPS Off button is pressed for three seconds with Bypass not
available, the UPS enters Load PowerĆOff mode.
If the Bypass mode was entered from Normal mode, wait approximately one minute
before trying to return to Normal mode. The UPS waits for internal voltages to bleed
down before proceeding to Normal mode of operation. Press the UPS On button once
to return to the Normal mode.
Load Power-Off Mode
To switch to Load PowerĆOff from Bypass mode, hold the UPS Off button for three
seconds. The alarm sounds while the UPS Off button is held, and the Bypass indicator
goes off when the bypass voltage is removed from the load. Press the UPS On button
once to return to Bypass mode.
If Bypass is not enabled or the Bypass indicator is blinking (indicating that Bypass is
not available), the UPS enters Load PowerĆOff mode from Normal mode. To switch to
Load PowerĆOff from Normal mode, hold the UPS Off button for three seconds. The
alarm sounds while the UPS Off button is held, and the Normal indicator goes off when
the voltage is removed from the load. The UPS waits for internal voltages to bleed
down before proceeding to Normal mode of operation. Press the UPS On button once
to return to the Normal mode.
Load PowerĆOff can also be entered by turning off (O) the output breaker.
Audible Alarm
An audible alarm sounds a pulsing tone when the UPS is in Overload or OnĆBattery
mode. When there is one minute or less of battery time remaining, a constant tone
sounds. The alarm also sounds a constant tone if the UPS is
on battery and the
UPS battery is disconnected (battery breaker is open or battery disconnected).
Bypass Plus
The UPS Bypass Plus feature contains two features in one: Automatic Bypass and
Maintenance Bypass. The UPS Bypass Plus features are available only when the
Bypass Configuration switch is enabled; this switch is factoryĆconfigured according to
your order.
Bypass operation requires that input and output voltage, frequency, and phase
displacement are the same. If the UPS is operating as a voltage and/or frequency
converter, bypass must be disabled. See Final Configuration" on page 45.
Automatic Bypass
The UPS automatically transfers the protected equipment directly to the utility AC
power, provided the bypass source is available, when one of the following conditions is
true:
Load current is between 106% to 124% of rating for 10 minutes, 125% to 149% for
30 seconds, or greater than 150% for 10 cycles.
UPS internal temperature exceeds safe operating range.
UPS output falls outside of the specified limits of voltage.
Output real power exceeds specified limits.
Load current inrush (surge) exceeds peak current capability.
Summary of Contents for powerware plus
Page 1: ... OPERATOR S MANUAL ...
Page 12: ...Powerware Plus 12 Operation ...
Page 35: ... Powerware Plus 12 Operator s Manual 164200090 Rev E 35 ...
Page 52: ...Description Outline Drawing PWP 18 Drawing No 110719045 Revision A Sheet 1 of 1 ...
Page 53: ...Description Oneline and Installation PWP 18 Drawing No 110719046 Revision A1 Sheet 1 of 2 ...
Page 54: ...Description Oneline and Installation PWP 18 Drawing No 110719046 Revision A1 Sheet 2 of 2 ...
Page 57: ...Description Three Phase PDM Installation PWP 18 Drawing No 110719090 Revision A1 Sheet 1 of 1 ...
Page 58: ...Description PWP18 Schematic Drawing No 110712322 Revision A Sheet 1 of 1 ...
Page 59: ...Description I O Outline and Installation PWP18 Drawing No 110719176 Revision B Sheet 1 of 1 ...
Page 60: ...Description I O Cabinet Oneline PWP 18 Drawing No 110719175 Revision C1 Sheet 1 of 5 ...
Page 61: ...Description I O Cabinet Oneline PWP 18 Drawing No 110719175 Revision C1 Sheet 2 of 5 ...
Page 62: ...Description I O Cabinet Oneline PWP 18 Drawing No 110719175 Revision C1 Sheet 3 of 5 ...
Page 63: ...Description I O Cabinet Oneline PWP 18 Drawing No 110719175 Revision C1 Sheet 4 of 5 ...
Page 64: ...Description I O Cabinet Oneline PWP 18 Drawing No 110719175 Revision C1 Sheet 5 of 5 ...