8 Installation
Powerware
®
Plus 12 Operator's Manual (164200090 Rev E)
34
Installing the UPS and Battery Cabinets
Only qualified service personnel (such as a licensed electrician) should
perform the UPS installation. Risk of electrical shock.
To perform the Plus 12 installation, you need the following tools: a 5/16
I
and a 1/4
I
hexĆnut driver. Make sure that you read all of the caution and warning statements in
Safety Considerations" beginning on page
before performing the installation.
If your UPS is connected to a remote battery provided by another manufacturer,
disregard all references to battery cabinets in this section and see Installing Remote
Batteries" on page 49 for more information on installation and configuration.
The following instructions assume you have already removed the UPS and battery
cabinets from the pallets according to the unloading instructions on the outside of the
shipping box.
Use the following procedure to set up the UPS and battery cabinets:
. Place the UPS and battery cabinets near the operating site. Make sure the air
vents and exhausts are free of obstructions and the UPS is not near a heat
source or in direct sunlight.
It is recommended to allow a minimum of 24
I
of space on the left side of
the unit for access by qualified service personnel and a minimum of 8
I
of
space on the rear side for proper ventilation.
. Remove the joining kit hardware from the shipping carton. The hardware kit
should contain four joining brackets (one notched) and eight #10Ć32
.50
large hexĆhead screws.
. Remove the mounting plates from the pallets (see Figure 5).
1/4
I
Bolts
Mounting Plate
Pallet
. A seismic installation of the UPS requires that the mounting plates be bolted to
the floor. See Figure 6 for a detailed drill and mounting pattern. If a seismic
installation is not required, it is not necessary to bolt the mounting plates to
the floor.
For Zone 4, it is recommended to use 5/16
I
selfĆdrill bolts and hardware
with 1 5/16
I
minimum embedment for 3000PSIĆstrength concrete. Refer to
your local building codes for seismic mounting requirements.
Summary of Contents for powerware plus
Page 1: ... OPERATOR S MANUAL ...
Page 12: ...Powerware Plus 12 Operation ...
Page 35: ... Powerware Plus 12 Operator s Manual 164200090 Rev E 35 ...
Page 52: ...Description Outline Drawing PWP 18 Drawing No 110719045 Revision A Sheet 1 of 1 ...
Page 53: ...Description Oneline and Installation PWP 18 Drawing No 110719046 Revision A1 Sheet 1 of 2 ...
Page 54: ...Description Oneline and Installation PWP 18 Drawing No 110719046 Revision A1 Sheet 2 of 2 ...
Page 57: ...Description Three Phase PDM Installation PWP 18 Drawing No 110719090 Revision A1 Sheet 1 of 1 ...
Page 58: ...Description PWP18 Schematic Drawing No 110712322 Revision A Sheet 1 of 1 ...
Page 59: ...Description I O Outline and Installation PWP18 Drawing No 110719176 Revision B Sheet 1 of 1 ...
Page 60: ...Description I O Cabinet Oneline PWP 18 Drawing No 110719175 Revision C1 Sheet 1 of 5 ...
Page 61: ...Description I O Cabinet Oneline PWP 18 Drawing No 110719175 Revision C1 Sheet 2 of 5 ...
Page 62: ...Description I O Cabinet Oneline PWP 18 Drawing No 110719175 Revision C1 Sheet 3 of 5 ...
Page 63: ...Description I O Cabinet Oneline PWP 18 Drawing No 110719175 Revision C1 Sheet 4 of 5 ...
Page 64: ...Description I O Cabinet Oneline PWP 18 Drawing No 110719175 Revision C1 Sheet 5 of 5 ...