3005831-2019-04-01.fm
Technical electrical connections (EXcon control
58/64
10.3.1 Digital inputs
Master Din1 (fire thermostat)
• Potential free contact, which trips in case of fire.
• Fire thermostat
• Smoke detector
• Fire thermostat
Master Din3 (external start/stop)
• Potential free contact, which trips in case of stop.
• BMS unit
• PIR sensor
Master Din4 (fire warning unit)
• Potential free contact, which trips in case of fire.
Master Din5 (cooling fault)
• Potential free contact, which trips in case of fault.
• Cooling pump fault
• Cooling unit fault
Master Din6 (external high speed)
• Potential free contact, which closes at high speed
• Contact timer
• PIR sensor
• BMS unit
• Extended operation pressure
10.3.2 Analogue inputs
Master Ain1 (common supply air)
• Pressure transducer, VAV sensor, 0–10 V
Master Ain2 (common extract air)
• Pressure transducer, VAV sensor, 0–10 V
• CO2
Master Tin1 (room temperature)
• PT1000 room sensor
Master Tin2 (water coil temperature)
• PT1000 sensor for built-in return water from water heating coil.