Wt.025.055.002.Ua.iM.0814
ManUal Chlorinator - 500lB/24hr
23
eVoQUa
W3t110693
4.8
Dirty Water Strainer
A strainer is required in the water line ahead of the injector to avoid plugging
of the injector throat ports by foreign material. If sufficient material is allowed
to build up on the strainer surface, the resultant pressure drop across the
strainer reduces the injector operating water pressure. If the pressure drop is
excessive, the injector will not be able to induct the required gas flow. Regular
periodic inspection and cleaning of the strainer will minimize this possibility.
4.9
Differential Regulating Valve (See Dwg. 25.152.001.011)
• Removal and Disassembly
a. Unscrew tubing union nut.
b. Unscrew plug (1). Remove and discard gasket (2).
WARNING: SPRING IS IN A COMPRESSED CONDITION. DISASSEMBLE
CAREFULLY TO PREVENT FORCEFUL EJECTION OF PARTS AND POSSIBLE
SEVERE PERSONAL INJURY.
c. Unscrew and remove valve body (3). Remove and discard gasket (2).
d. Push stem holder (4) out of diaphragm. Remove and discard O-ring
(10).
e. Unscrew and remove seat unit (8). Remove and discard gasket (7).
• Reassembly
a. The residue that accumulates on the valve seat can be removed with
warm water and a detergent. Pipe cleaners or soft brushes may fa-
cilitate cleaning, but wire brushes, scrapers, and the like should be
avoided as they will damage the parts.
b. Wipe a thin film of Halocarbon grease onto all O-rings before reas-
sembling.
c. Apply a thin film of fluorocarbon oil (No. 6.3, Halocarbon Products) to
gasket (2) before assembling.
d. Reassemble in the reverse order of disassembly.
!
Summary of Contents for Wallace & Tiernan V-2000 Series
Page 11: ...EVOQUA W3T110693 WT 025 055 002 UA IM 0814 MANUAL CHLORINATOR 500lb 24hr...
Page 12: ......
Page 17: ......
Page 26: ......
Page 32: ...WT 025 055 002 UA IM 0814 MANUAL CHLORINATOR 500lb 24hr 18 EVOQUA W3T110693...
Page 33: ......
Page 60: ......
Page 91: ......
Page 93: ......
Page 94: ...CHLORINE HANDLING MANUAL Cl2 BOOK NO WT 025 000 001 UA IM 0614 W3T98244...