Wt.025.055.002.Ua.iM.0814
ManUal Chlorinator - 500lB/24hr
9
eVoQUa
W3t110693
2.14
Leak Check
After the vacuum regulator(s) is in place, and before the gas tubing that will
connect it to the control module is installed, check for gas leaks as directed in
the instruction book provided with vacuum regulator.
WARNING: TO AVOID POSSIBLE SEVERE PERSONAL INJURY OR EQUIP-
MENT DAMAGE, DO NOT TOLERATE ANY GAS LEAKS. LEAKS ALWAYS GET
PROGRESSIVELY WORSE AND MUST BE CORRECTED PROMPTLY.
NOTE: The vacuum line extending from the control module to the vacuum
regulator must not exceed the distance (as determined on the graph, see
Dwg. 25.052.190.030) for the standard tubing and pipe sizes given. If neces-
sary, tubing or pipe can be installed that will not give more than five inches
of water differential between the module and vacuum regulator at maximum
feed rate. Note that the equivalent length of the fittings must be added to the
tubing length to obtain the total equivalent length as shown on the graph.
!