WARNING LABELS AND TAGS
The following warning labels and tags have been attached to the equipment.
----------------------------------------------------------------------------------------------------
L2016:
TO AVOID POSSIBLE SEVERE PERSONAL INJURY FROM ELECTRI-
CAL SHOCK, TURN OFF POWER BEFORE SERVICING.
----------------------------------------------------------------------------------------------------
L2708:
CHLORINE, WHICH IS A HAZARDOUS CHEMICAL, IS PRESENT
IN THIS EQUIPMENT DURING NORMAL OPERATION. TO AVOID
POSSIBLE SEVERE PERSONAL INJURY OR DEATH, YOU MUST
OBSERVE THE FOLLOWING PRECAUTIONS:
1. When changing chlorine supply containers you must be
completely familiar with your local plant operating and
emergency procedures including the location and use of
a gas mask. Recommended emergency procedures can be
obtained from your chlorine supplier, the Chlorine Institute,
Inc., or similar organization.
2. Do not open the chlorine supply container valve more than
one complete turn. This will permit maximum discharge and
can be turned off quickly in the event of a leak.
3. On a routine daily basis, starting at the chlorine supply
container(s), thoroughly check all joints, connections, and
equipment for possible chlorine leaks and immediately cor-
rect any found. Do not tolerate any chlorine leaks.
4. Chlorine leaks never get better. Chlorine leaks always get
progressively worse if they are not promptly corrected.
5. Never re-use gaskets in chlorine piping systems. Always have
an adequate supply on hand and always use new gaskets of
the correct size and material as identified on the equipment
parts drawings.
6. Except in cases of leak detection or calibration adjustments,
the chlorine supply must be shut off at the supply container
valve(s) and the chlorine in the system completely exhausted
before servicing the equipment.
7. It is recommended practice to have an approved gas mask
available, which you have been trained to use, when mak-
ing chlorine leak checks and when changing chlorine supply
containers.
Summary of Contents for Wallace & Tiernan V-2000 Series
Page 11: ...EVOQUA W3T110693 WT 025 055 002 UA IM 0814 MANUAL CHLORINATOR 500lb 24hr...
Page 12: ......
Page 17: ......
Page 26: ......
Page 32: ...WT 025 055 002 UA IM 0814 MANUAL CHLORINATOR 500lb 24hr 18 EVOQUA W3T110693...
Page 33: ......
Page 60: ......
Page 91: ......
Page 93: ......
Page 94: ...CHLORINE HANDLING MANUAL Cl2 BOOK NO WT 025 000 001 UA IM 0614 W3T98244...