Figure 2 – Manifolding Cylinders
3.2 MAXIMUM LIQUID WITHDRAWAL RATE
The generally accepted alternate to manifolding ton con-
tainers is to withdraw liquid chlorine from the lower valve
and use an evaporator. By this means, a ton container can
be emptied in approximately five hours, which is equivalent
to 9600 lbs/24 hrs.
Liquid can be withdrawn from tank cars at up to nearly 8,000
pounds per hour, or 192,000 pounds per 24 hours.
3.2.1
MANIFOLDING FOR LIQUID WITHDRAWAL
WARNING: IN ACCORDANCE WITH CHLORINE INSTI-
TUTE RECOMMENDATIONS, DO NOT MANIFOLD TON
CONTAINERS FOR SIMULTANEOUS LIQUID CHLORINE
WITHDRAWAL. THIS MANIFOLDING CAN CAUSE OVER-
PRESSURIZATION AND RUPTURE.
3.3 CONTAINER VALVES
Standard cylinder and ton container valves are identical in
design, except that the cylinder valve includes a pressure
relief device. Cylinder valves are shown in Figure 3 and ton
container valves in Figure 4.
See Figure 5 for captive yoke type auxiliary container valves
(valve connection style #820, recognized by the Compressed
Gas Association as the only acceptable means of connecting
to container valves). The external threads on the container
valve are used only for securing the protective cap.
Figure 3 – Standard Cylinder Valve
Figure 4 – Standard Ton Container Valve
Figure 5 – Auxiliary Ton Container Valve
Summary of Contents for Wallace & Tiernan V-2000 Series
Page 11: ...EVOQUA W3T110693 WT 025 055 002 UA IM 0814 MANUAL CHLORINATOR 500lb 24hr...
Page 12: ......
Page 17: ......
Page 26: ......
Page 32: ...WT 025 055 002 UA IM 0814 MANUAL CHLORINATOR 500lb 24hr 18 EVOQUA W3T110693...
Page 33: ......
Page 60: ......
Page 91: ......
Page 93: ......
Page 94: ...CHLORINE HANDLING MANUAL Cl2 BOOK NO WT 025 000 001 UA IM 0614 W3T98244...