2.9
Injector Water Supply
The injector requires a supply of reasonably clean water. Equip the water supply
with a strainer, as indicated in the typical installation drawing in this section. The
pressure and quantity of water required varies from one installation to another.
2.10 Drain
A floor drain is always desirable to facilitate injector service and for the injector
drain relief valve (if installed).
2.11 Injector Discharge
A rigid PVC pipe or Evoqua Water Technologies solution hose is required between
the one-inch fixed throat injector discharge and the point of application. The
size depends on the size of the throat and tailway used in the injector. Solu-
tion hose may be connected directly to the injector tailway. If rigid PVC pipe is
used, a piece of straight pipe at least eight inches long should be coupled to
the end of the injector tailway before any elbows, tees, or Saunders valves are
used. This is to prevent any flow disturbances that could affect the hydraulic
performance of tailway connections (see Dwg. 25.200.003.010).
2.12 Point of Application
2.12.1
Main Connection
If the solution is to be applied in a main, a suitable pipe tap is required in the
main to accommodate the solution tube or diffuser.
2.12.2
Open Well
If the solution is to be applied in a basin, flume, channel, etc., where there is
no pressure, the line from the injector must be supported so that the open
end is submerged to the bottom of the chamber, if possible, or a minimum of
six feet, and is located in a nonstagnant area.
2.13
Vacuum Regulator
A vacuum regulator, which is a gas pressure reducing valve and check, is con-
nected to the control module inlet. Refer to the separate instruction book
supplied with the unit for installation instructions for the unit.
Summary of Contents for Wallace & Tiernan V-2000 Series
Page 11: ...EVOQUA W3T110693 WT 025 055 002 UA IM 0814 MANUAL CHLORINATOR 500lb 24hr...
Page 12: ......
Page 17: ......
Page 26: ......
Page 32: ...WT 025 055 002 UA IM 0814 MANUAL CHLORINATOR 500lb 24hr 18 EVOQUA W3T110693...
Page 33: ......
Page 60: ......
Page 91: ......
Page 93: ......
Page 94: ...CHLORINE HANDLING MANUAL Cl2 BOOK NO WT 025 000 001 UA IM 0614 W3T98244...