S10k
Description
3.
21
3.5
Technical Data
Dosing accuracy
class 4 (according to VDI/VDE 3513 Bl. 2)
Flowmeters for chlorine
3" version: 24 g/h to 4 kg/h
5" version: 60 g/h to 10 kg/h
also refer to chapter 7.3
V notch plug
24 g/h to 10 kg/h Cl
2
Control range
20 : 1
Operating water
max. 16 bars at 38°C
max. 10 bars at 55°C
Minimum operating vacuum
minus 540 mbar at the injector at maximum gas flow
Inlet pressure at the vacuum de-
mand valve
minimum 1,4 bar, maximum 13,5 bar
Ambient temperature
+2° to +50°C
Airborne noise emission
does not exceed 70dB(A)
Contact pressure gauge
0...12 bar (g),
resistant up to 19.2 bar (g)
contact closed without pressure
contact opens at 2.4 bars (g) with rising pressure
contact closes at 1.5 bar (g) with falling pressure
max. load 6...24 VDC/VAC
5...100 mA, max 3 W
Heating (optional)
operating temperature 60 °C
protection IP 65
power consumption 20 W at 230 V
5 W at 115 V
Summary of Contents for WALLACE & TIERNAN S10k
Page 1: ...WALLACE TIERNAN GAS FEEDER S10k INSTRUCTION MANUAL ...
Page 2: ...2 WT 025 200 000 DE IM 0517 S10k Please note Original manual ...
Page 6: ...6 WT 025 200 000 DE IM 0517 Contents S10k ...
Page 22: ...22 WT 025 200 000 DE IM 0517 Description S10k 3 ...
Page 90: ...90 WT 025 200 000 DE IM 0517 Drawings S10k 7 7 4 2 Anti syphon injector W3T171368 1 ...
Page 93: ...S10k Drawings 7 93 ...
Page 94: ...94 WT 025 200 000 DE IM 0517 Drawings S10k 7 7 4 3 Injector W3T171369 3 4 ...
Page 96: ...96 WT 025 200 000 DE IM 0517 Drawings S10k 7 7 4 4 Antisyphon Injektor W3T171370 3 4 ...
Page 99: ...S10k Manufacturer declaration 8 99 8 Manufacturer declaration ...
Page 100: ...100 WT 025 200 000 DE IM 0517 Manufacturer declaration S10k 8 ...