3. Description
3.1
Design
The system consists of the following main components:
•
The separately mounted injector (6) for the generation of the
operating vacuum and for the mixing of the gas with the water.
•
The vacuum demand valve (1) is connected directly to the Cl
2
or SO
2
gas cylinder or to the gas manifold. It only opens when
the vacuum created by the injector is sufficient.
For the use with carbon dioxide a pressure reducing valve to
13.5 bar (g) is necessary.
•
The gas dosing unit (2) connected to the vacuum demand
valve via the vacuum line.
It includes the flowmeter to display the gas flow and the V-
notch plug to adjust the gas flow.
Dosage can be switched on and off by selenoid valves in the water
supply line or by booster pump.