51
70
AH7
30
Humidity Alarm delay and probe saturation.
0..240 min
N.
PAR.
DEF.
FANS
MIN... MAX.
71
F0
4
Evaporator Fan Mode during Normal Operation. With F0=0
it is possible to manage cycles with F11-F12 rd2-rd3 rh2-
rh3.
0 = Con cicli; 1 = Accese; 2 = ON per carichi on;
3 = Termoregolate (F1 relativo alla regolazione
temperatura); 4 = Termoregolate se carico ON
(F1 relativo alla regolazione temperatura)
72
F1
5
Evaporator Fan Adjustment Threshold with F0=3 or 4
-99..+99 °C/F
73
F2
0
Evaporator Fan Mode during Defrosting
0 = OFF; 1 = ON; 2 = secondo F0
74
F3
0
Evaporator Fan maximum Downtime after Dripping
0..15 min
75
F7
5
Setpoint-referred threshold for fan restart after defrosting
-99..+99 ° C/F
76
F8
2
Evaporator Setpoint differential
0 1..15 ° C/F
77
F9
5
Evaporator fan turning-off delay since compressor has
turned off
0..240 s
78
F11
60
Fan ON Time without adjustment with F0=0. F11=0 fans
remain idle
0..240 s
79
F12
60
Fan OFF Time without adjustment with F0=0. F12=0 and
F11>0 fans always turned on
0..240 s
N.
PAR.
DEF.
CONDENSER FAN
MIN... MAX.
80
Fc1
25
Condenser Fan OFF Threshold
0..99 ° C/F
81
Fc2
5
Condenser Fan ON Differential SET+Fc2
0 1..15 ° C/F
82
Fc3
5
Condenser Fan Turning-off Delay
0..240 " s
N.
PAR.
DEF.
DIGITAL INPUTS
MIN... MAX.
83
i1
0
Display Lock with Open Door and after closing it.
0..240 min
84
i2
15
Alarm warning delay since opened door
-1..120 min
85
i3
15
Inhibition Adjustment Maximum Time with Open Door accor-
ding to ic1=7/8/9 configuration
-1..120 min
86
i5
0
Multifunction Input Alarm Delay
0..120 min
87
i6
60
Pr3=0 and ic3=1 pressure. Consider i8 events since first
occurrence for manual reset
0..120 min
88
i7
60
ic1=5 Thermal Event Count Interval. Consider i8 events
since first occurrence for manual reset
0..120 min
89
i8
1
Digital Input Event Count for pressure switch a/o Thermal
Alarm. 0= always automatic 1 = always manual .
0..15
N.
PAR.
DEF.
AUXILIARY RELAY
MIN... MAX.
90
u6
0
Auxiliary Output Configuration. Manual control by AUX key.
0 = caldo; 1 = freddo; 2 = manuale
91
u7
0.0
Auxiliary setpoint if "u6= 0 or 1".
-99..+99 ° C/F
92
u8
1.0
u7 auxiliary set differential.
0 1..15 ° C/F
N.
PAR.
DEF.
DIG IN CONFIGURATION
MIN... MAX.
93
iC1
8
Digital input 1 functions. Functions 7 8 and 9 refer to mi-
croswitch.
0 = disabilitato; 1 = allarme multifunzione; 2 =
reservato; 3 = riservato; 4 = stand-by; 5 = termica
1; 6 = termica 2; 7 = compressore e ventole
spente luce accese; 8 = ventole spente luce
accesa; 9 = luce accesa
94
iP1
0
Microswitch Input Activation
0=chiuso o 1=aperto
95
iC3
0
Digital input 3 function
0= disabilitato; 1= pressostato alta
96
iP3
0
Multifunction input 3 Activation
0=chiuso o 1=aperto
N.
PAR.
DEF.
DIGITAL OUTPUTS
MIN... MAX.
97
uc1
4
Configures K1 relay (Comp)
0 = disabilitato; 1 = umidità rH; 2 = deumidifica
drH; 3 = allarme; 4 = compressore1; 5 = caldo;
6 = ventola condensatore; 7 = on/stand-by; 8 =
cambio aria; 9 = luce; 10 = compressore 2; 11
= ventole evaporatore; 12 = sbrinamento; 13 =
riservato; 14 = riservato; 15 = ausiliario
98
uc2
5
Configures K2 relay (heat)
0..15
99
uc3
9
Configures K3 relay (light)
0..15
100
uc4
1
Configures K4 relay (dehumid)
0..15
101
uc5
11
Configures K5 relay (Evap_Fan)
0..15
102
uc6
12
Configures K6 relay (defrost.)
0..15
N.
PAR.
DEF.
KEYBOARD
MIN... MAX.
103
POF
1
Enables ON/Stand-by key
0=no 1=si