EVER UPS SINLINE RT / RT XL series instruction manual
2017-04-26 12:41
Pomoc Techniczna, tel.: +48 61 6500 400
www.ever.eu
72
PARAMETERS \ TYPE
SINLINE
RT XL 650
SINLINE
RT XL 850
SINLINE
RT XL
1250
SINLINE
RT XL
1650
SINLINE
RT XL
2250
SINLINE
RT XL
3000
Part number
W/SRTXR
T-
000K65/00
W/SRTXR
T-
000K85/00
W/SRTXR
T-
001K25/00
W/SRTXR
T-
001K65/00
W/SRTXR
T-
002K25/00
W/SRTXR
T-
003K00/00
Output Power (Apparent / Active)
1)
650 VA
650 W
850 VA
850 W
1250 VA
1250 W
1650 VA
1650 W
2250 VA
2250 W
3000 VA
3000 W
MECHANICAL SPECIFICATIONS
Dimensions - Rack (H x W x D)
88 x 440 x 430 mm
132 x 440 x 460 mm
132 x 440 x
630 mm
Dimensions
– Tower (H x W x D)
440 x 88 x 430 mm
(UPS)
450 x 260 x 430 mm
(UPS + 2 supports for
tower position)
440 x 132 x 460 mm (UPS)
450 x 304 x 460 mm (UPS + 2
supports for tower position)
440 x 132 x
630 mm
(UPS)
450 x 304 x
630 mm
(UPS + 2
supports
for tower
position)
Net Weight
18 kg
26 kg
28 kg
42 kg
Gross Weight
20 kg
28,5 kg
30,5 kg
45 kg
Transport Dimensions (H x W x D)
197 x 547 x 545 mm
247 x 547 x 595 mm
247 x 547 x
765 mm
Position in which devices transported
Horizontal
Output cables maximum length
< 10 m
PROTECT
Input over current protection
Short-circuit protection
–
Circuit breaker
10 A / 250 V AC
Short-circuit protection
– Circuit breaker
16 A / 250 V AC
Surge Protection
Output over current protection
Electronic short-circuit and overload protection
DC over current (internal batteries)
Over current
DC over current (external battery input)
Over current
ACCESSORY AND EXTRA FUNCTIONS
Power supply connection
1 x IEC 320 C14 (10 A)
1 x IEC 320 C20 (16 A)
Output connection (number and type of
sockets )
3 x IEC320 C13 (10 A)
2 x PL
3 x IEC320 C13 (10 A) - controllable
3 x IEC320 C13 (10 A)
1 x IEC320 C19 (16 A)
2 x PL
Signalling
Acoustic and optical; LCD graphic display, LED
Communications interfaces
USB HID, SNMP/HTTP
LAN filter
– RJ45
LAN 1 Gbit/s
Software
PowerSoft Professional
CERTIFICATION
Declarations
CE
Standards
PN-EN 62040-1:2009, PN-EN 62040-2:2008
Note
: The manufacturer reserves the right to change the above listed parameters without notice.
* Charging time up to 90% battery capacity, following discharge with load equal to 80% Pmax (until the UPS switches off).
REMARKS:
1)
To ensure normal operation of the UPS unit, the load at its output should not exceed 80% of the value given in the chart. A
power reserve is necessary to maintain continuity of operation of connected appliances in case of momentary surges of load
current.
2)
The Rack Kit is available as an option.
3)
Constant exposure of the device to environment temperature over +25°C results in reducing battery life.
4)
Maximum allowed load the UPS unit will decrease as the altitude above the sea level increases over the specified limit.
Summary of Contents for SINLINE RT