3.
Undo the screws of the expansion slot cover (
Fig. 49a
).
4.
Insert the card, making sure it is aligned properly (
Fig. 49b
).
5.
Install the card slot cover to the rear panel (
Fig. 49c
).
6.
Connect an external EPO circuit - a fire protection breaker - to the card's
connector (
Fig. 49d
).
7.
Press and keep the
key on the UPS unit's front panel depressed for over 1
second to switch the device on.
8.
Switch on the UPS logically with the control panel (MENU; CONTROL sub-menu;
UPS Enabled).
9.
If the card has been correctly installed and identified by the UPS, the
Temp.EPODiss -
temporary EPO input deactivation (1 min.) parameter appears
in the CONTROL sub-menu.
Fig. 49: Installation of the card in the UPS