EVER UPS SINLINE RT / RT XL series instruction manual
11
www.ever.eu
Pomoc Techniczna, tel.: +48 61 6500 400
2017-04-26 12:41
E) Transport and packaging requirements
Exercise particular care when transporting the device.
Heavy equipment must be moved by at least two or more persons.
UPS units may be transported only in their original packaging boxes to ensure
adequate protection against shocks, vibrations and impact.
The unit should be operated and stored in conditions meeting the requirements in
the product specification. UPS units must be stored in a dry room with suitable
ventilation.
If a UPS is to be stored over a longer period of time, its batteries must be
recharged at least every 6 months. The recharging procedure must always be
recorded and documented.
Always make sure to check the date when recharging is due. Do not use the UPS
unit if the deadline has passed and the batteries have not been recharged. If this
occurs, contact service support.
Summary of Contents for SINLINE RT
Page 1: ......