Installation guidelines for the POWERLINE GREEN 33 LITE UPS units in parallel/redundant operation 

 

2016-10-27 11:56

 

Technical support

, tel.: +48 61 6500 400

 

www.ever.eu

 

INSTALLATION GUIDELINES 

Consider the device weight when choosing the installation site. The UPS units shall 

only  be  operated  in  rooms  where  the  dust,  temperature,  and  humidity  levels  are 

within  the  device  specifications.  Appropriate cooling  conditions must  be  ensured for 

the UPS units to work properly. For this reason, the ventilation openings of the UPS 

units must be kept clear and open at all times, and the clearance between each UPS 

unit  and  other  objects  shall  not  be  less  than  30 cm  (see  Table  1  for  the  minimum 

requirements). 

The  parameters  relevant  to  the  installation  guidelines  for  specific  UPS  models  are 

shown in Table 1. 

 

CAUTION!

  It  is  forbidden  to  install  the  appliance  near  flammable 

materials! 

Once  the  devices  have  been  positioned,  use  additional  two  assembly  fixtures  per 

each UPS to increase its mechanical stability. To do this, loosen the four (4) M8 bolts 

located  in  the  central  bottom  part  of  the  device.  Locate  the  fixtures  carefully  and 

fasten them to the device with the previously removed bolts (see the UPS Instruction 

Manual).  

Table 1. Installation guidelines for the POWERLINE GREEN 33 LITE 10-60 kVA UPS. 

PARAMETERS / MODEL 

POWERLINE GREEN 33 

Model 

10k 

Model 

15k 

Model 

20k 

Model 

30k 

Model 

40k 

Model 

50k 

Model 

60k 

Apparent / active power 

10 kVA 

10 kW 

15 kVA

 

12 kW 

20 kVA 

16 kW 

30 kVA

 

24 kW 

40 kVA

 

32 kW 

50 kVA

 

40 kW 

60 kVA  

45 kW 

POWER SUPPLY PARAMETERS 

Power system topology 

3P5W 

Rated voltage 

3 x 400 V AC 

Rated current 

16 A 

 

19 A 

25 A 

37 A 

50 A 

62 A 

70 A 

Rated frequency 
input 

50 Hz 

Minimum input wire size  

2,5 mm

2

 

4 mm

2

 

6 mm

2

 

16 mm

2

 

16 mm

2

 

25 mm

2

 

35 mm

2

 

Mains line 
protection 

Switch fuse 

- Fm

 

 

20 A gG 

25 A gG 

32 A gG 

50 A gG 

63 A gG 

80 A gG 

100 A gG 

BYPASS line 
protection 

Switch fuse 

- Fm

 

 

20 A gG 

25 A gG 

32 A gG 

50 A gG 

63 A gG 

80 A gG 

100 A gG 

OUTPUT PARAMETERS 

Output system topology 

3P5W 

Rated output voltage 

3 x 400 V AC 

Rated current 

15 A 

22 A 

29 A 

44 A 

58 A 

73 A 

87 A 

Minimum output wire size 

2,5 mm

2

 

4 mm

2

 

6 mm

2

 

16 mm

2

 

16 mm

2

 

25 mm

2

 

35 mm

2

 

Output line 
protection 

Switch fuse 

- Fout

 

 

20 A 

25 A 

32 A 

50 A 

63 A 

80 A 

100 A 

Summary of Contents for POWERLINE GREEN 33 LITE

Page 1: ......

Page 2: ...echnical support tel 48 61 6500 400 www ever eu 2 TABLE OF CONTENTS TABLE OF CONTENTS 2 SAFETY REMARKS 3 REQUIREMENTS FOR PREPARATION OF THE POWER SUPPLY AND RECEIVER SYSTEM 3 INSTALLATION GUIDELINES 6 ELECTRICAL SYSTEM 8 CONNECTING THE CONTROL AND SIGNAL LINES 11 COMMUNICATION BUS 12 TECHNICAL ACCEPTANCE 13 NOTES 13 ...

Page 3: ...rge This require proper transport and handling facilities an adequate number of helpers a forklift truck and properly dimensioned handling routes CAUTION Contact the Technical Service if any damage is found that may affect proper performance of the devices B Location CAUTION Selection of the installation site and assurance of proper operating conditions for the devices are the user s responsibilit...

Page 4: ...r systems The systems shall be designed and erected only by properly licensed and qualified personnel CAUTION The user shall ensure that the electrocution protection system meets the applicable requirements of local laws CAUTION Do not connect the PE line to the UPS units with copper cable tips The power supply and receiver lines of the UPS units shall be isolated It is recommended to specifically...

Page 5: ...mmended to install an external bypass system for the service bypass the topology of which matches the connection diagram of the UPS see the instruction manual for the external bypass system for operating and maintenance purposes The bypass system will enable servicing and maintenance of the devices without power interruptions The connection system shall be 3 or 5 wire depending on the UPS model CA...

Page 6: ... this loosen the four 4 M8 bolts located in the central bottom part of the device Locate the fixtures carefully and fasten them to the device with the previously removed bolts see the UPS Instruction Manual Table 1 Installation guidelines for the POWERLINE GREEN 33 LITE 10 60 kVA UPS PARAMETERS MODEL POWERLINE GREEN 33 Model 10k Model 15k Model 20k Model 30k Model 40k Model 50k Model 60k Apparent ...

Page 7: ...ature 1 0 to 40 C Storage temperature 0 to 40 C Moisture 95 Elevation 1000 m MECHANICAL PARAMETERS Dimensions height width depth 895 x 435 x 855 mm 1150 x 485 x 855 mm 1150 x 485 x 855 mm UPS weight 2 265 kg 320 kg 340 kg Minimum operating clearance 3 Front 200 mm Sides 100 mm Back 300 mm Note The manufacturer reserves the right to change the above parameters without notice NOTES 1 5 to 35 C for U...

Page 8: ...ording to the diagram shown in Fig 1 If a non original module is used install a 100 A 440 V DC fuse on the positive and negative lines Figure 1 Installation diagram of the POWERLINE GREEN 33 LITE 10 60 kVA UPS units in the parallel redundant system Installation diagram symbols Fm1 Fb1 Fout1 Fm2 Fb2 Fout2 Fsb Switch fuses the switch fuse Fb is an optional accessory Qout Qsb Switch disconnectors PP1...

Page 9: ...shown in Table 2 Table 2 Safeguards and wire sizes for the system SYSTEM POWER OUTPUT Fsb Qout Qsb B C POWERLINE 33 LITE 20 kVA 32 A gG 32 A 4 mm2 4 mm2 POWERLINE 33 LITE 30 kVA 50 A gG 63 A 10 mm2 10 mm2 POWERLINE 33 LITE 40 kVA 63 A gG 63 A 16 mm2 16 mm2 POWERLINE 33 LITE 45 kVA 80 A gG 80 A 16 mm2 16 mm2 POWERLINE 33 LITE 50 kVA 80 A gG 80 A 16 mm2 16 mm2 POWERLINE 33 LITE 60 kVA 100 A gG 100 A...

Page 10: ... LITE 60 kVA 100 A gG 35 mm2 25 mm2 16 mm2 CAUTION Use LgY wires for the UPS cables CAUTION Follow the phase rotation order when collecting the power supply line This applies to all components of the BYPASS switchboard and the UPS connection This UPS has been designed for operation in TN systems The exact requirements are specified for a local UPS switching room located directly at the device Foll...

Page 11: ...NG THE CONTROL AND SIGNAL LINES The POWERLINE GREEN 33 LITE UPS units have control inputs and programmable outputs The connection with these lines is shown with the diagrams in Fig 2 and the intended use of the lines is explained in the POWERLINE GREEN 33 LITE UPS Instruction Manual Figure 2 Connecting the control and signal wires on the POWERLINE GREEN 33 LITE 10 60 kVA UPS ...

Page 12: ...support tel 48 61 6500 400 www ever eu 12 COMMUNICATION BUS In order to assure data communication between the UPS devices in the parallel redundant system connect the UPS units with telecom lines an STP 4x2x0 5 cable with the diagrams in Fig 3 Figure 3 Connecting the data communication on the POWERLINE GREEN 33 10 60 kVA UPS ...

Page 13: ...tery voltage Measure the output voltage in the mains operating mode Test the UPS switching from mains to batteries without interruption of the load power supply if possible test at the target load of the UPS circuit Measure the output voltage in the battery operating mode If a bypass is installed train the personnel designated by the buyer in the bypass operation Confirm the completed technical ac...