Installation guidelines for the POWERLINE GREEN 33 LITE UPS units in parallel/redundant operation
2016-10-27 11:56
Technical support
, tel.: +48 61 6500 400
www.ever.eu
6
INSTALLATION GUIDELINES
Consider the device weight when choosing the installation site. The UPS units shall
only be operated in rooms where the dust, temperature, and humidity levels are
within the device specifications. Appropriate cooling conditions must be ensured for
the UPS units to work properly. For this reason, the ventilation openings of the UPS
units must be kept clear and open at all times, and the clearance between each UPS
unit and other objects shall not be less than 30 cm (see Table 1 for the minimum
requirements).
The parameters relevant to the installation guidelines for specific UPS models are
shown in Table 1.
CAUTION!
It is forbidden to install the appliance near flammable
materials!
Once the devices have been positioned, use additional two assembly fixtures per
each UPS to increase its mechanical stability. To do this, loosen the four (4) M8 bolts
located in the central bottom part of the device. Locate the fixtures carefully and
fasten them to the device with the previously removed bolts (see the UPS Instruction
Manual).
Table 1. Installation guidelines for the POWERLINE GREEN 33 LITE 10-60 kVA UPS.
PARAMETERS / MODEL
POWERLINE GREEN 33
Model
10k
Model
15k
Model
20k
Model
30k
Model
40k
Model
50k
Model
60k
Apparent / active power
10 kVA
10 kW
15 kVA
12 kW
20 kVA
16 kW
30 kVA
24 kW
40 kVA
32 kW
50 kVA
40 kW
60 kVA
45 kW
POWER SUPPLY PARAMETERS
Power system topology
3P5W
Rated voltage
3 x 400 V AC
Rated current
16 A
19 A
25 A
37 A
50 A
62 A
70 A
Rated frequency
input
50 Hz
Minimum input wire size
2,5 mm
2
4 mm
2
6 mm
2
16 mm
2
16 mm
2
25 mm
2
35 mm
2
Mains line
protection
Switch fuse
- Fm
20 A gG
25 A gG
32 A gG
50 A gG
63 A gG
80 A gG
100 A gG
BYPASS line
protection
Switch fuse
- Fm
20 A gG
25 A gG
32 A gG
50 A gG
63 A gG
80 A gG
100 A gG
OUTPUT PARAMETERS
Output system topology
3P5W
Rated output voltage
3 x 400 V AC
Rated current
15 A
22 A
29 A
44 A
58 A
73 A
87 A
Minimum output wire size
2,5 mm
2
4 mm
2
6 mm
2
16 mm
2
16 mm
2
25 mm
2
35 mm
2
Output line
protection
Switch fuse
- Fout
20 A
25 A
32 A
50 A
63 A
80 A
100 A