Installation guidelines for the POWERLINE GREEN 33 LITE UPS units in parallel/redundant operation 

 

www.ever.eu

 

Technical support

, tel.: +48 61 6500 400

 

2016-10-27 11:56

 

SAFETY REMARKS 

Read and understand the safety remarks and guidelines in the (full) Instruction 

Manual of this UPS before attempting any switching operations. 

REQUIREMENTS FOR PREPARATION OF THE POWER 

SUPPLY AND RECEIVER SYSTEM

 

A) 

Shipping requirements.

 

 

CAUTION!

  Extreme  caution  is  required  during  shipping,  unloading  and 

installation of the devices. 

  Transport the UPS units in the upright position as indicated on the packaging. 

  Protect the devices against weather (i.e. protect from rain). 

  Prolonged  shipping  or  storage  below  0 

C  and/or  above  25 

C  is  NOT 

recommended due to the battery life and the condensation hazard. 

  The  devices  are  heavy  and  large.  This  require  proper  transport  and  handling 

facilities  (an  adequate  number  of  helpers,  a  forklift  truck  and  properly 

dimensioned handling routes). 

 

CAUTION! 

Contact  the  Technical  Service  if  any  damage  is  found  that 

may affect proper performance of the devices. 

B) 

Location

 

 

CAUTION! 

Selection  of  the  installation  site  and  assurance  of  proper 

operating conditions for the devices are the user's responsibility. 

  Install  the  UPS  units  in  a  separate  room  (to  isolate  the  constant  noise  during 

operation and protect the devices from unauthorised access). 

  Do  not  expose  the  devices  to  extreme  (high  and/or  low)  temperatures.  Extreme 

temperatures may shorten the battery life (the optimum temperature range is +18 

to +25 

ºC). 

  Do  not  install  the  devices  in  rooms  with  dusty,  corrosive  and/or  flammable 

atmosphere  or  where  the  atmospheric  humidity  is  high  (the  recommended 

humidity is 90% without condensation). 

  If the devices are installed on false/technical access floors, consider the structural 

strength of the installation location. 

Summary of Contents for POWERLINE GREEN 33 LITE

Page 1: ......

Page 2: ...echnical support tel 48 61 6500 400 www ever eu 2 TABLE OF CONTENTS TABLE OF CONTENTS 2 SAFETY REMARKS 3 REQUIREMENTS FOR PREPARATION OF THE POWER SUPPLY AND RECEIVER SYSTEM 3 INSTALLATION GUIDELINES 6 ELECTRICAL SYSTEM 8 CONNECTING THE CONTROL AND SIGNAL LINES 11 COMMUNICATION BUS 12 TECHNICAL ACCEPTANCE 13 NOTES 13 ...

Page 3: ...rge This require proper transport and handling facilities an adequate number of helpers a forklift truck and properly dimensioned handling routes CAUTION Contact the Technical Service if any damage is found that may affect proper performance of the devices B Location CAUTION Selection of the installation site and assurance of proper operating conditions for the devices are the user s responsibilit...

Page 4: ...r systems The systems shall be designed and erected only by properly licensed and qualified personnel CAUTION The user shall ensure that the electrocution protection system meets the applicable requirements of local laws CAUTION Do not connect the PE line to the UPS units with copper cable tips The power supply and receiver lines of the UPS units shall be isolated It is recommended to specifically...

Page 5: ...mmended to install an external bypass system for the service bypass the topology of which matches the connection diagram of the UPS see the instruction manual for the external bypass system for operating and maintenance purposes The bypass system will enable servicing and maintenance of the devices without power interruptions The connection system shall be 3 or 5 wire depending on the UPS model CA...

Page 6: ... this loosen the four 4 M8 bolts located in the central bottom part of the device Locate the fixtures carefully and fasten them to the device with the previously removed bolts see the UPS Instruction Manual Table 1 Installation guidelines for the POWERLINE GREEN 33 LITE 10 60 kVA UPS PARAMETERS MODEL POWERLINE GREEN 33 Model 10k Model 15k Model 20k Model 30k Model 40k Model 50k Model 60k Apparent ...

Page 7: ...ature 1 0 to 40 C Storage temperature 0 to 40 C Moisture 95 Elevation 1000 m MECHANICAL PARAMETERS Dimensions height width depth 895 x 435 x 855 mm 1150 x 485 x 855 mm 1150 x 485 x 855 mm UPS weight 2 265 kg 320 kg 340 kg Minimum operating clearance 3 Front 200 mm Sides 100 mm Back 300 mm Note The manufacturer reserves the right to change the above parameters without notice NOTES 1 5 to 35 C for U...

Page 8: ...ording to the diagram shown in Fig 1 If a non original module is used install a 100 A 440 V DC fuse on the positive and negative lines Figure 1 Installation diagram of the POWERLINE GREEN 33 LITE 10 60 kVA UPS units in the parallel redundant system Installation diagram symbols Fm1 Fb1 Fout1 Fm2 Fb2 Fout2 Fsb Switch fuses the switch fuse Fb is an optional accessory Qout Qsb Switch disconnectors PP1...

Page 9: ...shown in Table 2 Table 2 Safeguards and wire sizes for the system SYSTEM POWER OUTPUT Fsb Qout Qsb B C POWERLINE 33 LITE 20 kVA 32 A gG 32 A 4 mm2 4 mm2 POWERLINE 33 LITE 30 kVA 50 A gG 63 A 10 mm2 10 mm2 POWERLINE 33 LITE 40 kVA 63 A gG 63 A 16 mm2 16 mm2 POWERLINE 33 LITE 45 kVA 80 A gG 80 A 16 mm2 16 mm2 POWERLINE 33 LITE 50 kVA 80 A gG 80 A 16 mm2 16 mm2 POWERLINE 33 LITE 60 kVA 100 A gG 100 A...

Page 10: ... LITE 60 kVA 100 A gG 35 mm2 25 mm2 16 mm2 CAUTION Use LgY wires for the UPS cables CAUTION Follow the phase rotation order when collecting the power supply line This applies to all components of the BYPASS switchboard and the UPS connection This UPS has been designed for operation in TN systems The exact requirements are specified for a local UPS switching room located directly at the device Foll...

Page 11: ...NG THE CONTROL AND SIGNAL LINES The POWERLINE GREEN 33 LITE UPS units have control inputs and programmable outputs The connection with these lines is shown with the diagrams in Fig 2 and the intended use of the lines is explained in the POWERLINE GREEN 33 LITE UPS Instruction Manual Figure 2 Connecting the control and signal wires on the POWERLINE GREEN 33 LITE 10 60 kVA UPS ...

Page 12: ...support tel 48 61 6500 400 www ever eu 12 COMMUNICATION BUS In order to assure data communication between the UPS devices in the parallel redundant system connect the UPS units with telecom lines an STP 4x2x0 5 cable with the diagrams in Fig 3 Figure 3 Connecting the data communication on the POWERLINE GREEN 33 10 60 kVA UPS ...

Page 13: ...tery voltage Measure the output voltage in the mains operating mode Test the UPS switching from mains to batteries without interruption of the load power supply if possible test at the target load of the UPS circuit Measure the output voltage in the battery operating mode If a bypass is installed train the personnel designated by the buyer in the bypass operation Confirm the completed technical ac...