EVCO S.p.A.
EVXV 800 range | Installer manual ver. 1.2 | Code 144XV800E124
page 39 of 66
d1
0
3
- - - -
1
1
type of defrosting
0 = electrical (the compressor will be
switched off during defrosting, the
defrosting output will be activated and
the evaporator fan will be switched off)
1 = hot gas (the compressor will be
switched on during defrosting, the
defrosting output will be activated and
the evaporator fan will be switched off)
2 = air (the compressor will be switched off
during defrosting and the defrosting
output
will
be
activated;
the
evaporator fan will be switched on,
independently from the conditions of
the door, i.e. independently from the
door micro switch input status)
3 = air with door open (the compressor will
be switched off during defrosting and
the defrosting output will be activated;
the evaporator fan will be switched on,
on condition that the door is open, i.e.
that is on condition that the door micro
switch is active and that the parameter
i0 is set at values different to 0)
d2
-50.0
99.0
°C/°F (1)
2.0
2.0
defrosting
end
temperature
(evaporator
temperature); also see parameter d3
d3
0
99
min
30
30
if parameter P4 is set at 0, duration of
defrosting
if parameter P4 is set at 1, maximum
duration of defrosting; see also parameter d2
0 = defrosting will never be activated
d4
0
1
- - - -
0
0
defrosting on start-up of blast chilling and
deep freezing
1 = yes
d5
0
99
min
30
30
defrosting delay on start-up of storing
0 = defrosting will be started on expiry of
the time established with parameter
d0