C3
0
240
s
0
0
compressor switch-on minimum duration
C4
0
240
min
10
10
duration of compressor switch-off during the
cabinet probe error (“
Pr1
” code) that occurs
during storage; see also parameter C5
C5
0
240
min
10
10
duration of compressor switch-on during the
cabinet probe error (“
Pr1
” code) that occurs
during post blast chilling storage; also see
parameter C4
C6
0
199.0
°C/°F (1)
80.0
80.0
condenser temperature above which the
blocked overheated condenser alarm is
activated (“
COH
” code)
C7
0
199.0
°C/°F (1)
90.0
90.0
condenser temperature above which the
blocked compressor alarm is activated (“
CSd
”
code)
C8
0
15
min
1
1
blocked compressor alarm delay (“
CSd
” code)
(5)
C9
0
240
min
30
30
duration of compressor switch-on during the
cabinet probe error (“
Pr1
” code) that occurs
during post deep freezing storage; also see
parameter C4
Par.
Min.
Max.
Unit
EVXV802
EVXV812
EVXV805
EVXV815
Defrosting (6)
d0
0
99
h
8
8
defrosting interval (7)
0 = defrosting will never be activated at
intervals