EUROSTER Q7TXRXGW Installation And Operation Manual Download Page 16

EUROSTER Q7TXRX

GW

 

 INSTALLATION AND OPERATION MANUAL

 

16

 

 

 

b.

 

NUMBER OF TX

 

 selecting from 1 to 6 determines how many thermostats will operate 

with one RX module 

Setting  a  value  of  1  enables  operation  with  several  RX  modules.  NUMBER  OF  RX  option  is 
available. 
Setting a value  of 2  or more disables the  NUMBER OF RX  option and requires  establishing 
the switching on and off priorities for the thermostats. The following additional options are 
available: 
TURN  ON  IF 

  determining  which  thermostats  should  switch  the  heating  device  on  and 

when. 

 

EACH 

 switching the heating device on when the temperature at each of the selected 

thermostats drops below the set point (an equivalent of the serial connection of wired 
thermostats). 

 

ANY 

 switching the heating device on when the temperature at any of the selected 

thermostats  drops  below  the  set  point  (an  equivalent  of  the  parallel  connection  of 
wired thermostats). 

TURN  OFF  IF 

  determining  which  thermostats  should  switch  the  heating  device  off  and 

when. 

 

EACH 

 switching the heating device off when the preset temperature is reached at 

each of the selected thermostats (an equivalent of the parallel connection). 

 

ANY 

  switching  the  heating  device  off  when  the  preset  temperature  is  reached  at 

any of the selected thermostats (an equivalent of the serial connection). 

The  priorities  of  switching  on  or  off  are  selected  with  the  knob  by  turning  it  to  select  the 
proper no. in the EACH or ANY item. Any, but only one, of these options may be assigned to 
switching the device on and one to switching it off. 
E.g.  when 

turn  on  if 

  each

  is  set  and  only  no. 3  is  selected,  then  the  receiver  will  only 

switch  on  the  heating  device  if  the  temperature  drops  below  the  preset  one  in  the  three 
rooms with thermostats no. 1, 2 and 3.  
When 

turn  off  if 

  any

  is  set  and  no. 4  is  selected,  then  the  receiver  will  switch  on  the 

heating if the preset temperature is reached at least at one of thermostats no. 1, 2, 3 or 4, 
even if it will not be reached at the other ones. 
Usually  the  priorities  are  set  as  in  standard  wired  connections:  the  serial  one  (turn  on  if: 
each 

  turn  off  if:  any)  or  the  parallel  one  (turn  on  if:  any 

  turn  off  if:  each).  It  is  also 

possible  to  set  the  priorities  that  are  impossible  in  simple  wired  connection:  EACH  for 
switching on and EACH for switching off with the selection of all paired thermostats. It is also 
possible  to  set  a  number  for  switching  on  and  a  different  one  for  switching  off.  Then,  all 
others are not involved in switching on or off. Please remember that switching off is superior 
to  switching  on.  If  ANY  is  set  for  the  switch  off  along  with  a  number  greater  than  for  the 
switch on, then regardless of the priority (each or any) set for the switch on, all thermostats 
must require heating in order to make the receiver switching the device on. 
It  is  possible  to  introduce  settings  enabling  switching  the  heating  on  only  when  the 
temperature at all thermostats will be lower and switching it off when the temperature will 
be  reached  at  the  first  one  only  (switch  on  if:  each  6 

  switch  off  if:  each  1).  It  is  also 

possible to introduce settings enabling only the first thermostat to switch the heating on and 
switch it off only when the temperature raises at all thermostats (switch on: each 1 

 switch 

off:  each  6).  Should  you  experience  any  problems  with  setting  priorities  we  recommend 
contacting our service.

 

c.

 

NUMBER OF RX

 

 selecting from 1 to 6 determines how many receivers will cooperate 

with one thermostat 

The receivers will simultaneously switch the connected devices on and off. 

Summary of Contents for Q7TXRXGW

Page 1: ...TAT MAINTENANCE Do not use the thermostat in rooms with excessive humidity significant dustiness or with presence of caustic or flammable vapors If necessary wipe it carefully with a damp cloth Do not...

Page 2: ...e battery compartment II USER FUNCTIONS 1 CONTROL OF THE THERMOSTAT a Display icons and operating window 1 Hour 2 Strength of radio communication between the thermostat and the receiver 3 Text box 4 C...

Page 3: ...fter pressing OK shortly when the display backlight is switched off If the thermostat cooperates with several receivers then the displayed signal strength is the signal strength of the most distant th...

Page 4: ...sensor only e RX receiver The receiver is equipped with a pass through socket enabling connecting a boiler or other device to the power supply It is not a controllable socket It is a simple 230 V soc...

Page 5: ...A will be displayed and the connected device will be switched on for 20 minutes every 3 h 2 BASIC SETTINGS The main menu consists of three basic items MODES 1 PROGRAMS 2 SERVICE 3 The menu items with...

Page 6: ...P1 23 C 06 00 am 08 30 am P2 28 C 08 30 am 03 00 pm P3 22 C 03 00 pm 11 00 pm P4 25 C 11 00 pm 06 00 am Sat Sun P1 23 C 06 00 am 11 00 am P2 22 C 11 00 am 04 00 pm P3 23 C 04 00 pm 11 00 pm P4 25 C 1...

Page 7: ...24 h The thermostat provides two methods of manual temperature setting a First method selecting an exact temperature for one of the three preset duration values It enables selecting the exact temperat...

Page 8: ...ll days of the week 1 2 3 4 5 6 7 are flashing Select the proper day or group of days and confirm After selecting the device will automatically proceed to the next item EDIT item 202 b EDIT item 202 p...

Page 9: ...se remember there will be a pause in heating in the place of the deleted range Adding a new range with starting and ending hours completely overlapping another range also deletes the previous one A ra...

Page 10: ...TO mode Detection of a rapid drop of ambient temperature switches the heating device off for the preset time If frost protection temperature is not switched on item 308 NO then airing mode limits the...

Page 11: ...mes and temperatures to be selected with the button see II User functions point 3 TEMPERATURE three temperatures of manual setting factory setting 18 C 20 C and 22 C DURATION three duration values of...

Page 12: ...as established and repeated When learning is active item 306 YES the thermostat records the temperature and time when it was modified If similar temperatures differing by no more than 0 4 C will be se...

Page 13: ...g days to properly calculate times for various temperatures thus for the first days the calculated times may not be enough to achieve precisely the preset temperatures at established times Usually the...

Page 14: ...he settings entered in the technician s menu neither does it reset the date and time It deletes all settings in the SERVICE menu along with the programmed ranges 12 AIR CONDITIONING item 312 switch fr...

Page 15: ...y algorithms to the particular configuration without the need to modify them manually in the service menu RADIO item 3 enables pairing devices establishing number of transmitters or receivers assignin...

Page 16: ...mperature drops below the preset one in the three rooms with thermostats no 1 2 and 3 When turn off if any is set and no 4 is selected then the receiver will switch on the heating if the preset temper...

Page 17: ...sh the priorities and possibly select a channel In order to pair Enter PAIR item and press OK WAIT will be displayed Then hold the left button of the RX receiver for 3 s PROG will be displayed Then ho...

Page 18: ...he need to change over the cables push the right button shortly To switch on pairing hold the middle button longer To exit hold the left button longer V INSTALLATION AND CONNECTION 1 PROPER PLACE OF I...

Page 19: ...rate the front panel and the base 3 SAMPLE CONNECTION DIAGRAMS The following diagrams are simplified and do not cover all the elements necessary for the correct installation In arrangement with a 230...

Page 20: ...INSTALLATION AND OPERATION MANUAL 20 In arrangement with a central heating pump 1 CH boiler 2 CH pump 3 Heat consumer radiator 4 Electrical connection block 5 Euroster RXGW 6 Euroster Q7TX 7 Output c...

Page 21: ...e Mounting method thermostat stand receiver 230 V 50 Hz socket Thermostat weight without batteries thermostat without batteries 114 g receiver 359 g Warranty period 2 years Dimensions W H D mm the the...

Page 22: ...may be repaired exclusively by the manufacturer or by other party clearly authorized by the manufacturer 5 Warranty becomes invalidated in case of any mechanical damage incorrect operation and or maki...