
Instruction Manual ZHK
94/129
V07-19.0
The corresponding K-factors of the fan are shown in the fan-motor data sheet or on the technical
data sheet for the AHU. The data on the data sheet always refers to one fan.
The air density at the measuring point is to set up manually, depending on sea level, temperature
and humidity. In most cases, 1.2 kg/m³ is a suitable value.
Note:
If in the EUROCLIMA delivery a device for airflow measurement is included, then this must
be configured on site and this is responsibility of the client before, commissioning!
Airflow rate indicator type PREMASREG 7161
This airflow indicator is used by EUROCLIMA and is supplied with the AHU, if included in the
scope of delivery. The setting of the parameters must be made by the customer before commis-
sioning
. This means, it is the client’s responsibility
to complete this task in accordance with the en-
closed instructions of the manufacturer.
The display is programmed according to formula B. Correspondingly, the value kB specified on the
data sheet in the fan section or the technical data sheet for the AHU must be used.
If more than one fan is installed in the supply or exhaust air, then the following instructions must be
observed:
Fan execution
Displays in pcs.
Measuring points
Total air flow rate
2 fans 50 % + 50 %
1 display
Only the fan near-
est to the operating
side
Displayed value * 2
2 fans 100 % + 100 %
2 displays
Both fans sepa-
rately
Displayed value (pow-
ered fan)
>2 fans/fan walls
1 display
Only the fan near-
est to the operating
side
Displayed value * num-
ber of powered fans)
Table 11:
Notes for airflow rate indicators, which are included in the scope of delivery
Processing the pressure signal in other devices
Devices from other manufacturers may require a conversion of the K-value. Therefore, always ask
for the formula, which the device is using.
8.1.3
Heat exchanger
The heat exchangers, fittings and valves shall be tested for tightness.
Attention!
Refrigerant
If direct expansion heat exchangers or air cooled heat exchangers are installed, the system must
be filled with refrigerant after the complete assembly. In this case, a refrigeration engineer must ex-
ecute the installation and piping.
Water heat exchangers
Normal heating, cooling coils filled with water and additives for freeze and corrosion protection:
-
Open vent valve.
-
Water valve is initially only to open slightly, so that the coil will be slowly filled with water. To
avoid heat stress.
-
When the heat exchanger is filled, close the vent valve.
-
Water valve is to open fully, start the fan.
-
Subsequently, the entire piping system must be vented properly.
Summary of Contents for ZHK Series
Page 1: ...ZHK INSTRUCTION MANUAL ...