Instruction Manual ZHK
114/129
V07-19.0
Refrigerant contains fluorinated hydrocarbons indicated in the Kyoto Protocol with the following
global warming potential (GWP = Global Warming Potential), based on CO
2
(data from EN378 part
1):
-
R407C: GWP = 1650
-
R410A: GWP = 1980
-
R134A: GWP = 1300
The greenhouse potential and the amount of refrigerant used in the device determine the mainte-
nance interval of the device.
Example:
Specification: refrigerant R407C, capacity 30 kg
CO2 equivalent: 1650 x 30 kg = 49500 kg = 49.5 t
Maintenance
interval: 5 t ≤ 49.
5 t <50 t
→
at least every 12
Maintenance intervals for the corresponding limits are given in
9.11.2
Maintenance
-
Has to be performed only by qualified personal and at least once a year.
-
Has to be documented in supplied
Records for refrigeration circuit application in air-conditioning
units
. Also, local regulations must be observed.
Whole system:
-
Check pressures and temperatures of the system.
-
Pay attention to unusual operating noises and to possible vibrations.
-
Possible dust deposits around components have to be removed.
Compressor:
-
When the compressor is switched on, there must be oil visible through the sight glass (if present).
If oil is not visible, ensure that there has not been a loss of oil (even outside of the AHU is possi-
ble); Optionally pour oil directly by an oil pump into the compressor suction side. Only use oil that
is approved by the compressor manufacturer.
-
During standstill periods of the compressor operation, the compressor crankcase heater switches
on in order to avoid an accumulation of refrigerant in the oil. Too much refrigerant in the oil causes
a dilution of the oil, resulting in a loss of viscosity leading to reduced lubrication of all moving
parts. To start the compressor manually, it has to be proceeded as described in
chapter 8.2.2
Manually starting the compressor via EUROCLIMA control system
-
Follow the maintenance and inspection requirements of the compressor manufacturer. These
instructions are supplied by EUROCLIMA or can be ordered from EUROCLIMA.
Filter drier:
Each refrigeration circuit is equipped with a filter drier. If the refrigeration circuit has to be repaired,
the filter drier must be replaced.
Sight glass in liquid line and on receiver
Liquid line sight glass contains a moisture indicator for refrigerant, operating as follows:
Indicator green
=
dry
Indicator yellow
=
wet
If the indicator shows wet refrigerant, at least the filter drier must be changed. Further measures may
be necessary.