EUCHNER NZ.VZ Operating Instructions Manual Download Page 5

Operating Instructions Safety Switch NZ.VZ

EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de [email protected]

Subject to technical modifications; no r

esponsibility is accepted for the accuracy of this information. © EUCHNER GmbH + Co. KG

 094060-06-12/10 (translation of the original operating instructions)

Figure 2: Switching elements with switching functions and connector assignment

511
528

538

3131

2131

2121

View of connection side

for the safety switch

1

6

5

4

3

2

9

11

10

5

4

6

3

7

2

8

1

Door closed

Door open

Terminal assignment

plug connector

SR6

Terminal assignment

plug connector

SR11

Ordinal number of

switching contacts

Figure 2a

Figure 2b

View of connection side

for the safety switch

Fig. 4: Dimension drawing NZ2VZ-5... with plug connector SR6

Pg 11

ma

x

.

Inserted

Inserted

Figure 3: Dimension drawing NZ1VZ-... with cable entry

M=1,2Nm

M=1,2 Nm

b

a

M20x1,5

30

±0,1

60

±0,1

115

9,5

47

74

+1

6

16

5,3

16

32

42

40

+1

7,3

5,3

31

38

25

36

52

23

+4

0,3

0,3

a  Travel without operation:

actuator is in the guide slot, however a
function is not triggered.

b  Switching operation completed:

actuator must be inserted to this point
to ensure reliable switching. The
actuator must be withdrawn at least to
point 

for switching off.

EC declaration of conformity

The manufacturer named below herewith declares that
the product fulfills the provisions of the directive(s)
listed below and that the related standards have been
applied.
EUCHNER GmbH + Co. KG
Kohlhammerstraße 16
70771 Leinfelden-Echterdingen, Germany
Directives applied:

Machinery directive 2006/42/EC

Standards applied:

EN 60947-5-1:2004 + Cor.:2005 + A1:2009

EN 1088:1995+A2:2008

Leinfelden, July 2010
Dipl.-Ing. Michael Euchner
Director
Duc Binh Nguyen
Authorized representative empowered to draw up
documentation
The signed EC declaration of conformity is included
with the product.

Summary of Contents for NZ.VZ

Page 1: ...n Schutz vor Umgebungseinflüssen Voraussetzung für eine dauerhafte und einwand freie Sicherheitsfunktion ist der Schutz des Betäti gungskopfes vor eindringenden Fremdkörpern wie Spänen Sand Strahlmitteln usw Bei Lackierarbeiten den Betätigungsschlitz den Be tätiger und das Typenschild abdecken Elektrischer Anschluss Bei der Auswahl von Isolationsmaterial bzw Anschlusslitzen ist die Übertemperatur ...

Page 2: ...1 2 Nm b a M20x1 5 30 0 1 60 0 1 115 9 5 47 74 1 6 16 5 3 16 32 42 40 1 7 3 5 3 31 38 25 36 52 23 4 0 3 0 3 a Leerlaufweg Betätiger ist im Führungsschlitz jedoch ohne eine Funktion auszu lösen b Schaltvorgang beendet Betätiger muss bis zu diesem Punkt eingeführt werden um eine sichere Schaltung zu gewährleis ten Zum Ausschalten muss der Betätiger mindestens bis Punkt a zurückgezogen werden EG Konf...

Page 3: ...rzschlussstrom 100 A Verschmutzungsgrad extern nach EN 60947 1 3 Industrie Schaltstrom min bei Schaltspannung DC 24 V DC 12 V NZ VZ 511 10 mA NZ VZ 1 mA 10 mA Gebrauchskategorie nach IEC 60947 5 1 NZ VZ 511 AC 15 6A 230V DC 13 6A 24V NZ1VZ NZ2VZ 5 AC 15 4A 230V DC 13 4A 24V NZ2VZ 2 NZ2VZ 3 AC 15 4A 50V DC 13 4A 24V Konventioneller thermischer Strom Ith NZ VZ 511 6 A NZ VZ 4A Kurzschlußschutz Steue...

Page 4: ...g head Set the required direction Tighten the screws with a torque of 1 2 Nm Protection against environmental influences A lasting and correct safety function requires that the actuating head must be protected against the penetration of foreign bodies such as swarf sand blasting shot etc Cover the actuating slot the actuator and the rating plate during painting work Electrical connection When choo...

Page 5: ...Inserted Figure 3 Dimension drawing NZ1VZ with cable entry M 1 2Nm M 1 2 Nm b a M20x1 5 30 0 1 60 0 1 115 9 5 47 74 1 6 16 5 3 16 32 42 40 1 7 3 5 3 31 38 25 36 52 23 4 0 3 0 3 a Travel without operation actuator is in the guide slot however a function is not triggered b Switching operation completed actuator must be inserted to this point to ensure reliable switching The actuator must be withdraw...

Page 6: ...ircuit current 100 A Degree of contamination external acc to EN 60947 1 3 industrial Switching current min At switching voltage DC 24 V DC 12 V NZ VZ 511 10 mA NZ VZ 1 mA 10 mA Utilization category to IEC 60947 5 1 NZ VZ 511 AC 15 6A 230V DC 13 6A 24V NZ1VZ NZ2VZ 5 AC 15 4A 230V DC 13 4A 24V NZ2VZ 2 NZ2VZ 3 AC 15 4A 50V DC 13 4A 24V Conventional thermal current Ith NZ VZ 511 6 A NZ VZ 4A Short cir...

Page 7: ... la direction voulue Serrer les vis au couple de 1 2 Nm Protection contre les influences ambiantes La condition pour garantir une fonction de sécurité durable et parfaite est de protéger la tête d actionnement contre la pénétration de corps étrangers ex copeaux sable grenailles etc En cas de laquage couvrir l ouverture d actionnement l élément d actionnement et la plaque signalétique Raccordement ...

Page 8: ...imensions NZ1VZ avec entrée de câble M 1 2Nm M 1 2 Nm b a M20x1 5 30 0 1 60 0 1 115 9 5 47 74 1 6 16 5 3 16 32 42 40 1 7 3 5 3 31 38 25 36 52 23 4 0 3 0 3 a Course d approche Introduction de la languette sans manoeuvre de contact b Manoeuvre terminée La languette doit être introduite jusqu à ce point afin de garantir une commutation sûre Pour la mise hors circuit la languette doit être retirée au ...

Page 9: ...Z 5 Uimp 2 5 kV NZ2VZ 2 NZ2VZ 3 Uimp 1 5 kV Courant conditionnel de court circuit 100 A Degré de pollution externe selon EN 60947 1 3 industrie Pouvoir de coupure min à la tension de commutation DC 24 V DC 12 V NZ VZ 511 10 mA NZ VZ 1 mA 10 mA Catégorie d emploi IEC 60947 5 1 NZ VZ 511 AC 15 6A 230V DC 13 6A 24V NZ1VZ NZ2VZ 5 AC 15 4 A 230 V DC 13 2 A 24 V NZ2VZ 2 NZ2VZ 3 AC 15 4 A 50V DC 13 2 A 2...

Page 10: ...nto Girare nella direzione desiderata Serrare le viti con 1 2 Nm Protezione contro gli agenti ambientali Premessa necessaria per un corretto e durevole funzionamento in sicurezza è che nella testina di azionamento non entrino corpi estranei quali trucioli sabbia graniglia ecc Prima dei lavori di verniciatura coprire l intaglio di comando l azionatore e la targhetta di identificazione Collegamento ...

Page 11: ... con pressacavo M 1 2Nm M 1 2 Nm b a M20x1 5 30 0 1 60 0 1 115 9 5 47 74 1 6 16 5 3 16 32 42 40 1 7 3 5 3 31 38 25 36 52 23 4 0 3 0 3 a Corsa a vuoto L azionatore si trova nella fessura di guida ma non attiva alcuna funzione b Commutazione terminata L azionatore deve essere inserito fino nel punto indicato in modo da garantire la commutazione sicura Per la disattivazione l azionatore deve essere a...

Page 12: ...ente di cortocircuito condizionata 100 A Grado di inquinamento esterno secondo EN 60947 1 3 industria Corrente di commutazione min con tensione di commutazione DC 24 V DC 12 V NZ VZ 511 10 mA NZ VZ 1 mA 10 mA Categoria di impiego secondo IEC 60947 5 1 NZ VZ 511 AC 15 6A 230V DC 13 6A 24V NZ1VZ NZ2VZ 5 AC 15 4A 230V DC 13 4A 24V NZ2VZ 2 NZ2VZ 3 AC 15 4A 50V DC 13 4A 24V Corrente termica standard It...

Page 13: ... los tornillos del cabezal actuador Ajuste la dirección deseada Apriete los tornillos con 1 2 Nm Protección contra influencias ambientales La condición imprescindible para un funcionamiento de seguridad correcto y duradero es la protección del cabezal actuador contra la penetración de cuerpos extraños como virutas arena abrasivos etc Al efectuar trabajos de pintura cubra la ranura de accionamiento...

Page 14: ...onector SR6 Pg 11 max Insertado Insertado Figura 3 plano de dimensiones NZ1VZ con entrada de cable M 1 2Nm M 1 2 Nm b a M20x1 5 30 0 1 60 0 1 115 9 5 47 74 1 6 16 5 3 16 32 42 40 1 7 3 5 3 31 38 25 36 52 23 4 0 3 0 3 a Recorrido en vacío El actuador está en la ranura guía pero no activa ninguna función b Proceso de activación finalizado El actuador debe insertarse hasta este punto para garantizar ...

Page 15: ... de cortocircuito condicionada 100 A Grado de contaminación externa según EN 60947 1 3 industria Corriente de activación mín con tensión de conexión 24 V CC 12 V CC NZ VZ 511 10 mA NZ VZ 1 mA 10 mA Categoría de uso según IEC 60947 5 1 NZ VZ 511 CA 15 6A 230V CC 13 6A 24V NZ1VZ NZ2VZ 5 CA 15 4A 230V CC 13 4A 24V NZ2VZ 2 NZ2VZ 3 CA 15 4A 50V CC 13 4A 24V Corriente térmica convencional Ith NZ VZ 511 ...

Reviews: