22
Power Control Processor Configuration Manual
Emergency Setup
• Emergency Outputs: Allows you to assign each position to
be either “On” or off “– –” when the panic input is active.
• Emergency Level: The value that the emergency circuits
will activate to when the emergency input is active. Can be
set anywhere between 1%–100%. The default is 100%.
• Load Shedding: Determines what occurs to the loads in
the rack that are not part of the recorded emergency look.
Available options include On or Off, with a default of On.
- When set to Off, the circuits will remain at their last
control level at the time of emergency contact activation.
- When set to On, the circuits that are included in the emergency look will turn on to the
Emergency level. Any circuits that are not set to be included in the emergency look will turn off.
Quick Rack Setup
The “Quick Rack Setup” menu offers a simple, initial setup of
the panel and is available by default when the panel is
otherwise un-configured.
For additional setup or to quickly change a setting after initial
configuration, access “Quick Rack Setup” from the main
menu.
• Output Count: When Auto is selected, the numbering and arrangement of the outputs is
automatically detected by the presence or absence of breakers and relays. When a number is
entered in place of Auto, the rack assumes that number of relays. Any output positions where
relays or breakers are not detected are assumed to contain a single-pole option.
• DMX Start Address: Displays the first DMX address used for patching. The default is 1.
• sACN Universe: Displays the first sACN universe in the panel (1–63999).
• sACN Start Address: Displays the first sACN address in the panel (1–512).
• Space: Determines the space to which all relays or breakers in the rack will be assigned (1–255).
• Apply Changes* Only: Only the items that have been changed shall be applied.
• Apply All: All items will be applied regardless if they have been changed or not.
- For example, if a DMX start address of 510 is entered and Apply All is selected, the panel’s
auto-fill feature may causes consecutive addresses to extend beyond the allowed 512. In this
instance the panel will automatically unpatch all circuits with an invalid address by assigning
them to DMX zero.
- The same is true if an sACN address entry causes an address overflow. All relays or breakers
holding invalid addresses will be unpatched by assigning them to zero.
CAUTION:
The “Quick Rack Setup” operation will erase your rack’s configuration and
generate a new one. It is recommended to make a backup of your
configuration before entering this menu option.
Emergency Setup
Emergency Outputs:
Emergency Level:
100%
Load Shedding:
On
Quick Rack Setup
Output Count:
Auto
DMX Start Addr:
1
sACN Universe:
1
sACN Start Addr:
2
Space: 1
Apply Changes* Only
Apply All