Menu and Configuration
27
Contact Input
There are 24 contact inputs available in the panel. These inputs
can be configured for one of several actions.
• Contact: Displays the number of contact being configured,
1–24.
• Evaluate on boot: Determines whether the contact state is
evaluated on boot and the action configured for it is taken
at the time of boot.
• Space: Determines the space in which the selected action
will happen.
• On Open: Determine the action that occurs when the
contact is opened. The following options are available:
- None: No action will be taken when the contact opens.
- Off: Off will be activated in the selected space when the contact opens.
- Preset: The selected preset will be activated in the selected space when the contact opens.
- Sequence: The sequence will be activated in the selected space when the contact opens.
- Output to Full: The selected output range will be driven to full when the contact opens.
- Output to 0%: The selected output range will be driven to 0% when the contact closes.
• On Close: Determine the action that occurs when the contact is closed. The same actions are
available as listed above.
Timeclock
The Timeclock allows built-in timed event control for your system.
The Timeclock includes the following features:
• 24-hour astronomical timeclock with user-configurable daylight savings time (DST).
• Recurrence settings including everyday, weekday, weekends, and day of week.
• 50 field-programmable events including preset activate, sequence, and off.
• Manual control of presets with override capability.
• Current event manual “hold” up to two hours with the option to manually cancel before those
two hours expire.
• Automatic schedule resumption after a power loss.
• Holiday shut-off configuration by space.
H o l d s
A Hold can be triggered to override a scheduled event, preset, or sequence during normal operation.
When a Hold is active, regularly scheduled events are ignored. The timeclock interacts with the presets
and sequences to determine specific Hold behavior. The response differs depending on the scheduled
event and the type of Hold that is currently active.
When an active Hold is cleared, the originally scheduled event is restored. Any manual control without
an active Hold condition only temporarily changes the current state of the Echo system. The next event
will execute according to its schedule.
Timed Hold
A Timed Hold occurs when a scheduled event is interrupted by manually triggering a preset or
sequence. Set
Auto Timed Hold
within the
Schedule Events
Menu to dictate if an event responds to a
manually activated preset or sequence. See
A Timed Hold will automatically clear after two hours (120 min).
Contact Input
Contact: 1
Evaluate on boot:
No
Space:
1
On Open:
Preset
Preset: 1
On Close: Output to FL
Outputs: 1
thru
1