ETAtouch controller

then pauses until 10:15 am , restarts at 10:15 am,
pauses from 10:20 am to 10:30 am , and so on ...
until the end of the time window at 2:00 pm .

In this operating mode, the circulation pump
can  also  start  outside  of  the  time  window

when hot water is being tapped. This is useful if, for
example,  the  time  window  ends  at  8:00  pm   and
you shower at 9:30 pm . When you then turn on the
hot water briefly, the circulation pump starts, and
you  will  have  hot  water  for  showering  shortly
afterwards. 
This runtime (outside the time window) is set in the
text  menu  (parameter  [Circulation  pump  delay]).
Enter  the  same  value  as  parameter  [Circulation
runtime].

Heat exchanger

The  tap  symbol  next  to  the  heat
exchanger  is  only  displayed  if  the  fresh
water module is feeding hot water into the
water  mains.  The  temperature  shown
next to this is the temperature of the hot
water currently being supplied.

If no hot water is being supplied, the heat exchanger is
shown blue all the way through.

Circulation pump in operation

Optional: for [Circulation pump]

The  pump  symbol  next  to  the  heat
exchanger  appears  when  the  circulation
pump for hot water is in operation.

Timer [Stand-by times]

This is only displayed if option [Target value can
be set with rotary knob] is deactivated 

This  timer  displays  the  set  charging  times  of  the
current day for charging the hot water tank. These time
windows are displayed as a black bar in the timer.

Timer [Circulation times]

This only appears if a circulation pump is installed
and the [Self-learning] function is deactivated.

This timer displays the set times of the current day to
operate the circulation pump. These time windows are
displayed as a black bar in the timer.

10.1.1.2

Operating modes

Ready

No hot water is currently being taken.

Working

Hot water is currently being supplied.

Buffer cold

Hot water is being supplied, but the buffer is not hot
enough to reach the configured hot water temperature.

Primary return too warm

Hot water is being supplied, but the selected hot water
temperature  is  being  reduced  because  the  [Primary
return] temperature in the heat exchanger of the fresh
water module is too high.

Malfunction

A temperature sensor in the fresh water module has a
defect.

Circulation

The circulation pump is in operation.

Venting

The controller has found air in the fresh water module
and  automatic  venting  is  in  operation.  For  this,  both
pumps are operated at full speed for a short period of
time  to  remove  the  air  from  the  fresh  water  module.
This can also take place multiple times sequentially.

Emergency operation

The  fresh  water  module  is  in  emergency  mode
because the admixing pump is defective. Currently, hot
water is being delivered but it is only being produced
with the buffer pump. 

Without  the  admixing  pump,  calcification
protection  of  the  heat  exchangers  it  not

guaranteed.  Protracted  emergency  mode  can
therefore calcify the heat exchanger.

Ready (Emergency operation)

The  fresh  water  module  is  in  emergency  mode
because the admixing pump is defective.

Without  the  admixing  pump,  calcification
protection  of  the  heat  exchangers  it  not

guaranteed.  Protracted  emergency  mode  can
therefore calcify the heat exchanger.

Circulation

Circulation pump delay

Summary of Contents for Fresh water module 33

Page 1: ...2019 11 22 EN 0000000131 V 016 X 35 11 X 47 0 93994 004 Fresh water module Operating Instructions...

Page 2: ...ETA Heiztechnik Gewerbepark 1 A 4716 Hofkirchen an der Trattnach Tel 43 0 7734 22 88 0 Fax 43 0 7734 22 88 22 info eta co at www eta co at...

Page 3: ...et 18 5 Configuration 20 6 Electrical connections 22 6 1 Requirements 22 6 2 CAN bus installation 22 6 3 Circuit board EM C4 24 7 Commissioning 26 8 Information on cold water 28 8 1 General 28 8 2 Cal...

Page 4: ...nce with this safety instruction there is a risk of physical injury DANGER On non compliance with this safety instruction there is a risk of major physical injury 1 2 Warranty guarantee and liability...

Page 5: ...e practical experience without having the installation checked by a trained and responsible expert we exclude defects in our delivery and conse quential damages resulting from this cause from our warr...

Page 6: ...ical and electronic equipment RoHS 2 Directive Applied Standards EN 60335 1 2012 Household and similar electrical appliances Safety Part 1 General requirements IEC 61000 6 1 2 2005 Electromagnetic com...

Page 7: ...11 Optional circulation pump with safety valve 10 bar and drain cock to empty the hot water circulation line 12 Circuit board EM C Fig 3 2 Dimensions Technical data Tap output 33 litres minute with 4...

Page 8: ...Optional circulation pump with safety valve 10 bar and drain cock to empty the hot water circulation line 12 Circuit board EM C Fig 3 4 Dimensions Technical data Tap output 44 litres minute with 45 C...

Page 9: ...manual setting of the hot water temperature is defective Flashing RED 5x every 4 seconds Automatic venting by the admixing pump does not work There may be air in the primary circuit of the fresh water...

Page 10: ...same way the lime build up has little opportunity to form as it is purged from the plate heat exchanger as a result of the high flow speeds In order to protect the plate heat exchanger against calcifi...

Page 11: ...eat producer to the buffer The solenoid valve is connected to the circuit board EM C at the terminal S102 LZ The ouput of the buffer pump from the fresh water module must then be duplicated i e additi...

Page 12: ...12 www eta co at Information for installation Description Check the pipe dimensions lengths and number of fittings and calculate the line resistance...

Page 13: ...gth to limit pressure losses The length of the CAN Bus line supplied for connection to the boiler is 10 m The 3 temperature sensors for the buffer can be connected to the circuit board EM C of the fre...

Page 14: ...wall installation The fresh water module weighs approximately 20 kg Mounting the fresh water module on the buffer For mounting the fresh water module on the buffer a bracket with clamping jaws for 6...

Page 15: ...er module Keep this in fresh water module so that it is available if later a circulation set is retrofitted Fig 4 7 Joint Mounting the screw joints At the top mount the ball valve on the flow connecti...

Page 16: ...the buffer is shown in the following Establish the flow line from the buffer to the fresh water module Fig 4 11 Flow line to the fresh water module If a lateral connection is not possible the fresh wa...

Page 17: ...rs such as 15 mm CU or 1 2 galvanised for example then pressure shocks are to be expected In order to protect all components against pressure shocks we recommend fitting a small diaphragm pressure exp...

Page 18: ...n pump 4 Drain cock to bleed the hot water circulation line 5 Joint with 1 outer thread For the fresh water module 44 the joint is already included in the delivery scope of the fresh water module Keep...

Page 19: ...possible that the safety valve opens a little and begins to drip Similar to a pressure free under counter storage tank or a hot water tank If the water installation is designed with rigid pipes and n...

Page 20: ...FWM 2pumps function block this is already installed at the factory For monitoring purposes check whether this is shown in the Selected function blocks column for the circuit board EM C 0 in the functi...

Page 21: ...02 LZ and must be assigned manually Assigning terminal 1 In the Selected function blocks field first select the function block of the fresh water module FWM FWM 2pumps 2 Double tap at the buffer pump...

Page 22: ...it is safely isolated from supply CAUTION Flexible stranded conductors If flexible stranded conductors are not used for the wiring the contacts in the plug connections will be subjected to excessive m...

Page 23: ...of the same design e g two EM C are connected to one another via CAN bus those circuit boards must have different and consecutive node numbers In this way they are recognized in CAN bus and can be con...

Page 24: ...intended for motor ball valves of cascade systems in order to activate the subsequent fresh water module also referred to as Slave module This output can also be used for a solenoid valve in order to...

Page 25: ...ed control for buffer pump S603 PWM output Speed control for admixing pump S604 24 V input Flow sensor with temperature sensor S605A CAN bus From boiler S605B CAN bus Free X1 CAN Bus terminal resistor...

Page 26: ...en the hot water tap once more and carry out the steps again Carry on doing this until no more air escapes from the fresh water module Mounting the plastic cover Reattach the plastic cover following c...

Page 27: ...er in the fresh water module is minimized You can determine the required running time of the circulation pump in the following way Start the circulation pump in the control system by means of manual o...

Page 28: ...ven become irreparable Due to the fact that 1 litre of water contains about 18 mg of calcium for each dH the risk of calcifi cation increases with increasing water hardness One litre of water with 10...

Page 29: ...28 6 dH Corrosion is likely Conductance Water hardness Resistance Substance Standard heat exchanger soldered with copper solder INOX heat exchanger soldered with stainless steel brazing solder Appear...

Page 30: ...d 5 to 12 per cent acetic acid or 10 to 20 per cent formic acid is suitable for descaling purposes Both acids are available from drugstores Pay attention to the concen tration CAUTION Always pour the...

Page 31: ...way See the following description for this Operating modes for the circulation pump There are two ways to operate the circulation pump Either through automatic detection of the operating times self l...

Page 32: ...n pump is installed and the Self learning function is deactivated This timer displays the set times of the current day to operate the circulation pump These time windows are displayed as a black bar i...

Page 33: ...w screen on the Stand by times timer A screen opens Fig 10 1 Overview of hot water charging times Set the hot water temperature as low as possible to prevent limescale build up You can find further de...

Page 34: ...blocks with timers To set the charging times tap the timer in the overview An overview opens Fig 10 3 Overview Set the individual time windows and temperatures by tapping the lines Time slot 1 Time s...

Page 35: ...ETAtouch controller Up to software version X 35 X 35 A screen opens showing the individual days of the week Fig 10 6 Copying time windows Make your selection and press the Accept button to save...

Page 36: ...rning function often referred to as auto loop or manual specification of the operating times set time window Self learning function This is already set at the factory parameter Self learning to Yes Th...

Page 37: ...the Stand by times Daily plan button An overview screen opens Fig 10 7 Overview 1 Set time windows standby times 2 Select day of the week 3 Add another time window 4 Graphical representation of the ti...

Page 38: ...ion block with the Settings button Fig 10 8 Open the settings 2 Access the charge times of a particular day with the Charging times Daily plan button Fig 10 9 Access charging times 3 An overview scree...

Page 39: ...perature Fig 10 12 Reduced operation temperature settings In this example the desired hot water temperature outside the charging times is 30 C When loading times and temperatures of a day of the week...

Page 40: ...t water can briefly be hotter than the target temperature set Explanation of the Emergency operation only with buffer pump function Emergency operation of the fresh water module can be activated with...

Page 41: ...at the hot water pipe Then enter this time in parameter Circulation runtime During this time measurement no hot water may be tapped e g by sink shower because otherwise an incorrect time is measured E...

Page 42: ...42 www eta co at Simplified electrical connection overview 11 Simplified electrical connection overview...

Page 43: ...Simplified electrical connection overview 43 Frischwassermodul 93994 1 Frischwassermodul EM C S101 S103 S100 S602 S603 S604 S600 N L L N...

Page 44: ...www eta co at www eta co at downloads DOWNLOAD...

Reviews: