background image

20

www.eta.co.at

Configuration

5

Configuration

Content of this configuration

Only  the  steps  required  for  the  configuration  of  this
product are described below. The configuration of the
complete heating system is described in the "Configu-
ration" manual supplied with the boiler.

Required software version

The  configuration  of  the  fresh  water  module  "33"
requires  the  software  version  X.35.7  or  X.41.0  or
higher. An  update  must  be  performed  first  if  a  lower
version is installed.

The  fresh  water  module  "44"  requires  the
software version X.46.0 or higher. A configuration

with the previous software interface (up to X.35.X) is
therefore  not  possible.  But  the  fresh  water  module
works  independently,  even  without  a  CAN-bus
connection to the ETAtouch control.

Starting the configuration assistant

The  process  of  starting  the  configuration  assistant
differs depending on the installed software version.
Software version X.35.X and earlier

Increase the authorisation to [Service]. Then open
the [Toolbox] menu by pressing the 

 button and

the [Configure system] button.

Software version X.36.0 and later

In the system settings 

, increase the authori-

zation to [Service] and open the system configura-
tion menu with the [Systems configuration] button.
Start  the  configuration  assistant  with  the 
[Starting the assistant] button.

Description for software version X.36.0 and later

The following description and screen shots represent
the software interface of version X.36.0 and later.

Function block [FWM 2pumps] is already installed

To control the fresh water module using energy-saving
pumps, the circuit board [EM-C] features the separate
[FWM 2pumps] function block; this is already installed
at the factory.

For  monitoring  purposes,  check  whether  this  is
shown  in  the  [Selected  function  blocks]  column

for  the  circuit  board  [EM-C  0]  in  the  function  blocks
overview.

Adjusting options in function block [FWM 2pumps]

The  circulation  pump  is  already  configured  at  the
factory (=option [Circulation pump]) as well as the hot
water temperature settings via the potentiometer only
(=option [Target value can be set with rotary knob]). 

If, however, no circulation pump is installed or the
hot  water  temperature  should  be  set  with  the

ETATouch controller, these options must be deactivat-
ed.
This  is  done  by  selecting  the  fresh  water  module
function  block  from  the  [Selected  function  blocks]
column:

Open options. Deactivate the respective option in the
window that opens:

Press the [Accept] button to save.

Adding fresh water module as consumer

The fresh water module is connected to the buffer
as  an  additional  consumer  (together  with  the

heating circuits, for example). A separate connection is
not required. 
If there is not yet any connection between the buffer
and the heating circuit, a new connection must be set
up.  For  this  purpose,  press  the  [New  connection]
button and select the [Heating water] connection type.
Connect  the  fresh  water  module  (as  a  consumer)  to
the buffer (as a producer). See below for an example
with a heating circuit and the fresh water module:

Tab. 5-1: Example with heating circuit and fresh water 

module

If  there  is  already  a  connection  between  the
buffer  and  the  heating  circuits,  the  fresh  water

module must only be added to this connection as an
additional consumer. 

Selected function blocks

EM-C 0

FWM 2pumps

Circulation pump
Target value can be set with rotary knob

Connections

Heating water

Producers

GM-C 0: Buffer: HC/HWT

Consumers

EM-C 0: FWM: .
GM-C 0: HC: .

Summary of Contents for Fresh water module 33

Page 1: ...2019 11 22 EN 0000000131 V 016 X 35 11 X 47 0 93994 004 Fresh water module Operating Instructions...

Page 2: ...ETA Heiztechnik Gewerbepark 1 A 4716 Hofkirchen an der Trattnach Tel 43 0 7734 22 88 0 Fax 43 0 7734 22 88 22 info eta co at www eta co at...

Page 3: ...et 18 5 Configuration 20 6 Electrical connections 22 6 1 Requirements 22 6 2 CAN bus installation 22 6 3 Circuit board EM C4 24 7 Commissioning 26 8 Information on cold water 28 8 1 General 28 8 2 Cal...

Page 4: ...nce with this safety instruction there is a risk of physical injury DANGER On non compliance with this safety instruction there is a risk of major physical injury 1 2 Warranty guarantee and liability...

Page 5: ...e practical experience without having the installation checked by a trained and responsible expert we exclude defects in our delivery and conse quential damages resulting from this cause from our warr...

Page 6: ...ical and electronic equipment RoHS 2 Directive Applied Standards EN 60335 1 2012 Household and similar electrical appliances Safety Part 1 General requirements IEC 61000 6 1 2 2005 Electromagnetic com...

Page 7: ...11 Optional circulation pump with safety valve 10 bar and drain cock to empty the hot water circulation line 12 Circuit board EM C Fig 3 2 Dimensions Technical data Tap output 33 litres minute with 4...

Page 8: ...Optional circulation pump with safety valve 10 bar and drain cock to empty the hot water circulation line 12 Circuit board EM C Fig 3 4 Dimensions Technical data Tap output 44 litres minute with 45 C...

Page 9: ...manual setting of the hot water temperature is defective Flashing RED 5x every 4 seconds Automatic venting by the admixing pump does not work There may be air in the primary circuit of the fresh water...

Page 10: ...same way the lime build up has little opportunity to form as it is purged from the plate heat exchanger as a result of the high flow speeds In order to protect the plate heat exchanger against calcifi...

Page 11: ...eat producer to the buffer The solenoid valve is connected to the circuit board EM C at the terminal S102 LZ The ouput of the buffer pump from the fresh water module must then be duplicated i e additi...

Page 12: ...12 www eta co at Information for installation Description Check the pipe dimensions lengths and number of fittings and calculate the line resistance...

Page 13: ...gth to limit pressure losses The length of the CAN Bus line supplied for connection to the boiler is 10 m The 3 temperature sensors for the buffer can be connected to the circuit board EM C of the fre...

Page 14: ...wall installation The fresh water module weighs approximately 20 kg Mounting the fresh water module on the buffer For mounting the fresh water module on the buffer a bracket with clamping jaws for 6...

Page 15: ...er module Keep this in fresh water module so that it is available if later a circulation set is retrofitted Fig 4 7 Joint Mounting the screw joints At the top mount the ball valve on the flow connecti...

Page 16: ...the buffer is shown in the following Establish the flow line from the buffer to the fresh water module Fig 4 11 Flow line to the fresh water module If a lateral connection is not possible the fresh wa...

Page 17: ...rs such as 15 mm CU or 1 2 galvanised for example then pressure shocks are to be expected In order to protect all components against pressure shocks we recommend fitting a small diaphragm pressure exp...

Page 18: ...n pump 4 Drain cock to bleed the hot water circulation line 5 Joint with 1 outer thread For the fresh water module 44 the joint is already included in the delivery scope of the fresh water module Keep...

Page 19: ...possible that the safety valve opens a little and begins to drip Similar to a pressure free under counter storage tank or a hot water tank If the water installation is designed with rigid pipes and n...

Page 20: ...FWM 2pumps function block this is already installed at the factory For monitoring purposes check whether this is shown in the Selected function blocks column for the circuit board EM C 0 in the functi...

Page 21: ...02 LZ and must be assigned manually Assigning terminal 1 In the Selected function blocks field first select the function block of the fresh water module FWM FWM 2pumps 2 Double tap at the buffer pump...

Page 22: ...it is safely isolated from supply CAUTION Flexible stranded conductors If flexible stranded conductors are not used for the wiring the contacts in the plug connections will be subjected to excessive m...

Page 23: ...of the same design e g two EM C are connected to one another via CAN bus those circuit boards must have different and consecutive node numbers In this way they are recognized in CAN bus and can be con...

Page 24: ...intended for motor ball valves of cascade systems in order to activate the subsequent fresh water module also referred to as Slave module This output can also be used for a solenoid valve in order to...

Page 25: ...ed control for buffer pump S603 PWM output Speed control for admixing pump S604 24 V input Flow sensor with temperature sensor S605A CAN bus From boiler S605B CAN bus Free X1 CAN Bus terminal resistor...

Page 26: ...en the hot water tap once more and carry out the steps again Carry on doing this until no more air escapes from the fresh water module Mounting the plastic cover Reattach the plastic cover following c...

Page 27: ...er in the fresh water module is minimized You can determine the required running time of the circulation pump in the following way Start the circulation pump in the control system by means of manual o...

Page 28: ...ven become irreparable Due to the fact that 1 litre of water contains about 18 mg of calcium for each dH the risk of calcifi cation increases with increasing water hardness One litre of water with 10...

Page 29: ...28 6 dH Corrosion is likely Conductance Water hardness Resistance Substance Standard heat exchanger soldered with copper solder INOX heat exchanger soldered with stainless steel brazing solder Appear...

Page 30: ...d 5 to 12 per cent acetic acid or 10 to 20 per cent formic acid is suitable for descaling purposes Both acids are available from drugstores Pay attention to the concen tration CAUTION Always pour the...

Page 31: ...way See the following description for this Operating modes for the circulation pump There are two ways to operate the circulation pump Either through automatic detection of the operating times self l...

Page 32: ...n pump is installed and the Self learning function is deactivated This timer displays the set times of the current day to operate the circulation pump These time windows are displayed as a black bar i...

Page 33: ...w screen on the Stand by times timer A screen opens Fig 10 1 Overview of hot water charging times Set the hot water temperature as low as possible to prevent limescale build up You can find further de...

Page 34: ...blocks with timers To set the charging times tap the timer in the overview An overview opens Fig 10 3 Overview Set the individual time windows and temperatures by tapping the lines Time slot 1 Time s...

Page 35: ...ETAtouch controller Up to software version X 35 X 35 A screen opens showing the individual days of the week Fig 10 6 Copying time windows Make your selection and press the Accept button to save...

Page 36: ...rning function often referred to as auto loop or manual specification of the operating times set time window Self learning function This is already set at the factory parameter Self learning to Yes Th...

Page 37: ...the Stand by times Daily plan button An overview screen opens Fig 10 7 Overview 1 Set time windows standby times 2 Select day of the week 3 Add another time window 4 Graphical representation of the ti...

Page 38: ...ion block with the Settings button Fig 10 8 Open the settings 2 Access the charge times of a particular day with the Charging times Daily plan button Fig 10 9 Access charging times 3 An overview scree...

Page 39: ...perature Fig 10 12 Reduced operation temperature settings In this example the desired hot water temperature outside the charging times is 30 C When loading times and temperatures of a day of the week...

Page 40: ...t water can briefly be hotter than the target temperature set Explanation of the Emergency operation only with buffer pump function Emergency operation of the fresh water module can be activated with...

Page 41: ...at the hot water pipe Then enter this time in parameter Circulation runtime During this time measurement no hot water may be tapped e g by sink shower because otherwise an incorrect time is measured E...

Page 42: ...42 www eta co at Simplified electrical connection overview 11 Simplified electrical connection overview...

Page 43: ...Simplified electrical connection overview 43 Frischwassermodul 93994 1 Frischwassermodul EM C S101 S103 S100 S602 S603 S604 S600 N L L N...

Page 44: ...www eta co at www eta co at downloads DOWNLOAD...

Reviews: