6
www.eta.co.at
Read out node number
Preparation
2.2
Read out node number
Note down the node number of the defective
control panel
Reading the set node number is only required if
more than one control panel (BE-P) is present in
the system.
If several control panels are in the system, check the
set node number before removing the defective control
panel (if possible). Note it down so that the same node
number can be set after replacing. By default, the
boiler control panel always has the node number "0".
The following describes how the node numbers are
displayed on the different control panels.
Control panel "BE-P1" has a node switch on the
bottom.
Fig. 2-1: Node switch for "BE-P1"
From control panel "BE-P2", the node number is
only displayed in the ETAtouch control system.
Depending on the software version installed (up to
X.35.X or from X.36.0), the set node numbers are
displayed differently.
•
Up to software version X.35.X
On the control panel, press the
button and then
the [Software Version] button. The node number
set is displayed in the overview.
Fig. 2-2: Overview (up to X.35.X)
•
Software version X.36.0 and later
On the control panel, open the system settings
and press the
[Version overview] button. The
node number set is displayed in the overview.
Fig. 2-3: Overview (from X.36.0)
2.3
meinETA remote control
Delete "meinETA" registration
If there is a registration for "meinETA" on the defective
control panel, this must be deleted before the
exchange (if possible). Note down the access details
for "meinETA" in order to register the new control panel
after the exchange. See chapter
.
Summary of Contents for BE-P3