Defrost
Highlight “Defrost” in the parameters menu then press the
enter key to display the screen shown in figure 10.
Highlight the parameter you wish to change then enter
again to allow the parameter to be changed. Use the
up and down keys to change the value, then Esc to
save the setting, esc again to return to the parameters
menu. The adjustable ranges are:
Def. cyc. 30 to 90 Mins
Def.in. -30
°
C to 0
°
C
Def.out 2
°
C to 30
°
C
Max time 1 to 12 Mins
Please note that it would be unwise to change these values from the default values listed
later in this manual.
Save
Highlight “Save” in the parameters menu then press the enter
key to display the screen shown in figure 11. Press the up
and down keys to toggle between “1” and “0”.
Please
note, 1=On and 0 = off.
The default value is 1.
Disinfection
Please note that EN 8506 stipulates minimum temperature
and time for a weekly disinfection period.
To change these
parameters, highlight “Disinfection” in the parameters menu
then press the enter key to display the screen shown in figure
12. Press the up and down keys to highlight the
parameter you wish to change, enter to allow the
setting to be changed then the up and down keys to
change the value. Press Esc to save and Esc again to
return to the parameters screen.
Swell Value
Highlight “Swell Value” in the parameters menu then press the
enter key to display the screen shown in figure 13. Highlight
the parameter you wish to change then enter again to
allow the parameter to be changed. Use the up and
down keys to change the value, then Esc to save the
setting, esc again to return to the parameters menu. The
adjustable values are: Mode – either Auto or Manual,
Overheat Value -20
°
C to 20
°
C and Adjust Step 100 to
500N.