630502_4
DS
1400 Indoor Outdoor Installation
Prepare the Cavity
Based on the architectural details given below, prepare the wall cavity for the installation of the fireplace.
45°
53
0
m
in
cavity outlet vent
minimum open area
combined
120,000mm2
convected heat from
the fire
section through DS1400
with wall linings direct fixed
non-combustible sheet to
direct heat out of the cavity
- end panels not required
convected heat pathway
from outdoor extension kit
Typical framed external wall
with supports for non-combustible
linings
cavity inlet vent
minimum open area
combined
47,600mm2
standard alum. window
with IGU
Head Detail
Sill Detail
Intake vent
inclusion zone
Outlet vent
inclusion zone
cavity extension parts
20
0
m
in
cavity inlet vent
minimum open area
combined
47,600mm2
standard construction adhesive
to all sheet junctions
*refer to recommended materials
list
30
0
20
0
cavity outlet vent
minimum open area
combined
120,000mm2
non-combustible sheet to back
of lining and into opening of vent
i.e. 2 x 140mm by 170mm vents
i.e. 85mm by 1200mm vent