User Manual
esatto.house
18
19
Troubleshooting
NOTE: Please review the chart below before calling for service.
NORMAL OPERATION
• You may hear a pinging noise caused by water being picked up and thrown against the condenser on rainy days
or when the humidity is high. This design feature helps remove moisture and improve efficiency.
• You may hear the thermostat click when the compressor cycles on and off.
• Water will collect in the base pan during high humidity or on rainy days .The water may overflow and drip from
the outdoor side of the unit.
• The fan may continue to operate when the compressor has cycled off.
ABNORMAL OPERATION
Fault
Possible Cause
Solution
Air conditioner
does not start
• The air conditioner is
unplugged
• Make sure the air conditioner plug is pushed completely into
the outlet and switched on.
• The fuse is blown/circuit
breaker is tripped
• Check the house fuse/circuit breaker box and replace the fuse
or reset the breaker.
• Power failure.
• If power failure occurs, switch off and disconnect/unplug
the power cord. When power is restored, reconnect (plug
in) the power cord, switch on the power and wait 3 minutes
to restart the air conditioner to prevent tripping of the
compressor overload.
Air conditioner does not cool
as it should
• Airflow is restricted
• Make sure there are no curtains, blinds, or furniture blocking
the front of the air conditioner.
• The air filter is dirty.
• Clean the filter at least every 2 weeks.
See the operating instructions section.
• The room may have been hot.
• When the air conditioner is first turned on you need to allow
time for the room to cool down.
• Cold air is escaping
• Check for open furnace floor registers and cold air returns.
• Set the air conditioner’s vent to the closed position.
• Cooling coils have iced up
• See Air Conditioner Freezing Up below.
Air conditioner
freezing up
• Ice blocks the air flow and
stops the air conditioner from
cooling the room.
• Set the fan at MED or HIGH until the ice melts.
Specifications
Below outlines the technical specifications for your Esatto Air Conditioner.
Dimensions (W � D � H mm)
600 � 560 � 380mm
Net Weight
36.2kg
Gross Weight
39.2kg
Power Supply
220-240V, ~50Hz, 1Ph
Minimum norminal cross-sectional area of conductors:
Rated current of appliance (A)
Nominal cross-sectional area (mm
2
)
�3 and � 6
0.75
�6 and ≤ 10
1
�10 and ≤ 16
1.5
�16 and ≤ 25
2.5
Suggest Minimum Wire Size (AWG: American Wire Gage):
Appliance Amps
AWG Wire Size
10
18
13
16
18
14
25
12
30
10