Features
ENIP-2, manual, ENIP.411187.002. Rev. 11.2020
27
Display modules can be paired with ENIP-2 by panel or cabinet mounting.
For full information about display panels ENMI see
.
3.7
Real-time clock
ENIP-2 has real-time clock. It allows to save event logging and to transmit data with
timestamp over IEC 60870-5-101/104, Modbus or IEC 61850-8-1.
The following table gives all available sources for sync time.
Ethernet
IEC 60870-5-104, SNTP, sync module ENCS-2
RS-458
IEC 60870-5-101, sync module ENCS-2
Time sync may be UTC or local time.
Timestamp over IEC 60870-5-101/104 may transmit with UTC or local time (with sum-
mer/winter time).
All settings, including time source, validity checking and time zone are configured by
«
ES
Configurator
»
.
Time accuracy with synchronization is up to 500
µ
s. Without synchronization ENIP-2 has
up to 3 seconds error per day.
3.8
Event logging
ENIP-2 saves in non-volatile memory the following log files:
•
Event log (software update, configuration change, power supply on/off, diagnostic
messages); up to 40 last events with timestamp are available.
•
Digital signals log (status of internal and external digital inputs and outputs, thresh-
olds); 200 last events with timestamp are available.
Figure 3.5. Combined installation of ENIP-2 and ENMI