Features
ENIP-2, manual, ENIP.411187.002. Rev. 11.2020
20
Figure 3.2. Connection of ENIP-2 and ENMV
3.3.2
Digital inputs
ENIP-2 is equipped with 0, 4, 8 or 12 built-in digital inputs with debounce filter. Contacts
for digital inputs can be both wet and dry (fig. 3.3). Dry contacts are powered by built-in
24 V DC supply.
“wet” contacts
“dry” contacts
Figure 3.3. Wet and dry contacts for DI
ENIP-2 can contain up to 32 DI. These include its own DI (built-in) as well as DI from
extension ENMV modules connected to ENIP-2 via RS-485-2 (up to 4 modules).
ENIP-2 has events log of DI statuses. Each record of event log is marked with time stamp
with 1 ms resolution.
DI statuses are transferred over IEC 60870-5-101, IEC 60870-5-104 in Single point or
Double point.
Table 3.4
ENIP-2-XX/X-X-XX-X1
ENIP-2-XX/X-X-XX-
X1(220)
ENIP-2-XX/X-X-XX-32
Type
0, 4 or 8 wet contact
0, 4 or 8 wet contact
12 wet contact
Voltage
20…250 V DC
200…250 V AC
18…36 V DC
Current
2 mA
2 mA
2 mA