Features
ENIP-2, manual, ENIP.411187.002. Rev. 11.2020
19
3.3
Digital signals
The maximum number of digital signals (called
«
DIO
»
) for ENIP-2 is 32. These include DI,
DO, configurable setpoints, logical expressions, goose subscribers, diagnostics (table 3.2).
Every DIO is configured independently. For details see
«
ES Configurator manual
»
.
Table 3.2
DIO
Description
Digital output
Built-in or external DO
Digital input
Built-in or external DI
Setpoints
Configurable setpoints for any parameters.
Logical expressions
Use any DIO for switchgear interlocking protection.
Goose subscriber
Subscribe to GOOSE-messages IEC61850 8-1
Diagnostic
Errors monitoring
3.3.1
Digital outputs
ENIP-2 Standard and Compact provides switchgear equipment control using built-in dig-
ital outputs or using extension ENMV-1 modules, which are connected to RS-485-2 of
ENIP-2.
Table 3.3
ENIP-2 Standard
ENIP-2 Compact
Extension module
ENMV
Type
3 SSR output
3 (electroma high power
solid-state) relay output
electromagnetic relay
or SSR output
Maximum
voltage
300 V DC
250 V AC
250 V DC/AC
250 V AC
Maximum
current
100 mA DC/AC
impulse 200 ms
–
9
А
short impulse - 6
А
long impulse - 5
А
longtime - 1.3
А
100 mA DC/AC (SSR)
7 A AC (EMR)
For built-in DO use intermediate relay if current is more than 100 mA:
−
AC: Finder 55.33.8.230.0010, Relpol (R4-2014-23-5230-WT) or similar;
−
DC: Finder 55.33.9.220.0010, Relpol (R4-2014-23-1220-WT) or similar.
Four or less ENMV modules can be connected via RS-485-2 (1 ENMV-2-4/3R-220-
А
1 plus
3 ENMV-1 or 4 ENMV-1). One ENMV-1-4/3R can control only one electrical switch.
ENIP-2 and ENMV communicate via Modbus RTU protocol.
ENIP-2 supports
Single command (<45>), Double command (<46>) over IEC 60870-5-101
or IEC 60870-5-104 and Force Single Coil (the function code 5) over Modbus.