Appendix E Modbus RTU Communication Protocol
D01908R02.12
B-PRO User Manual 8700
Appendix E-3
Input 4 46-50 Trip
00818
0: Off (inactive)
1: On (active)
Input 4 46-51 Alarm
00819
0: Off (inactive)
1: On (active)
Input 4 46-51 Trip
00820
0: Off (inactive)
1: On (active)
Input 5 5LS-1 Output
00821
0: Off (inactive)
1: On (active)
Input 5 50LS-2 Output
00822
0: Off (inactive)
1: On (active)
Input 5 50BF-1 Trip
00823
0: Off (inactive)
1: On (active)
Input 5 50BF-2 Trip
00824
0: Off (inactive)
1: On (active)
Input 5 50 Trip
00825
0: Off (inactive)
1: On (active)
Input 5 51 Alarm
00826
0: Off (inactive)
1: On (active)
Input 5 51 Trip
00827
0: Off (inactive)
1: On (active)
Input 5 50N Trip
00828
0: Off (inactive)
1: On (active)
Input 5 51N Alarm
00829
0: Off (inactive)
1: On (active)
Input 5 51N Trip
00830
0: Off (inactive)
1: On (active)
Input 5 46-50 Trip
00831
0: Off (inactive)
1: On (active)
Input 5 46-51 Alarm
00832
0: Off (inactive)
1: On (active)
Input 5 46-51 Trip
00833
0: Off (inactive)
1: On (active)
Input 6 5LS-1 Output
00834
0: Off (inactive)
1: On (active)
Input 6 50LS-2 Output
00835
0: Off (inactive)
1: On (active)
Input 6 50BF-1 Trip
00836
0: Off (inactive)
1: On (active)
Input 6 50BF-2 Trip
00837
0: Off (inactive)
1: On (active)
Input 6 50 Trip
00838
0: Off (inactive)
1: On (active)
Input 6 51 Alarm
00839
0: Off (inactive)
1: On (active)
Input 6 51 Trip
00840
0: Off (inactive)
1: On (active)
Input 6 50N Trip
00841
0: Off (inactive)
1: On (active)
Input 6 51N Alarm
00842
0: Off (inactive)
1: On (active)
Input 6 51N Trip
00843
0: Off (inactive)
1: On (active)
Input 6 46-50 Trip
00844
0: Off (inactive)
1: On (active)
Input 6 46-51 Alarm
00845
0: Off (inactive)
1: On (active)
Input 6 46-51 Trip
00846
0: Off (inactive)
1: On (active)
87T Trip
00847
0: Off (inactive)
1: On (active)
87B-1 Trip
00848
0: Off (inactive)
1: On (active)
59-1 Trip
00849
0: Off (inactive)
1: On (active)
59-2 Trip
00850
0: Off (inactive)
1: On (active)
27-1 Trip
00851
0: Off (inactive)
1: On (active)
27-2 Trip
00852
0: Off (inactive)
1: On (active)
60 Alarm
00853
0: Off (inactive)
1: On (active)
81O-1 Trip
00854
0: Off (inactive)
1: On (active)
81O-2 Trip
00855
0: Off (inactive)
1: On (active)
81U-1 Trip
00856
0: Off (inactive)
1: On (active)
Read Coil Status (Function Code 01)
www
. ElectricalPartManuals
. com
Summary of Contents for 8700/BUS
Page 2: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Page 8: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Page 10: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Page 18: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Page 86: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Page 90: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Page 146: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Page 150: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Page 158: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Page 162: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...
Page 166: ...w w w E l e c t r i c a l P a r t M a n u a l s c o m...