Appendix K Bus Differential Function Setting Examples
D01908R02.12
B-PRO User Manual 8700
Appendix K-3
Settings Method
The clearest way to understand the proposed bus differential settings method
is through a specific example. Figure 3 illustrates normal load conditions.
Figure K.4: Bus transfer load
Settings are developed using simple steps:
1. Enter Winding/CT connection information
2. Determine the maximum bus transfer current
3. Choose a value for IRs
4. Calculate the Bus Base MVA
5. Determine the CT Saturation Block Timer
6. Enter settings in the B-PRO
1. Enter Winding/CT Connection Information
Enter Winding and CT connection information to match the specific bus pro-
tection application, as in the example of Figure 4.
Figure K.5: Winding/CT Connections Settings